H9 ASD Installation and Operation Manual
123
PG Input Point 2 Setting
Program
⇒
Frequency
⇒
Speed Reference Setpoints
This parameter is used to set the direction and speed of the PG input terminals
when the PG terminals are used as the control input.
This parameter sets the PG input signal that is associated with PG Point 2
Frequency.
This value is entered as 0% to 100% of the PG input signal range.
See PG Point 1 Setting for further information on this setting.
Direct Access Number — F236
Parameter Type — Numerical
Factory Default — 0
Changeable During Run — Yes
Minimum — 0
Maximum — 100
Units — %
PG Input Point 2 Frequency
Program
⇒
Frequency
⇒
Speed Reference Setpoints
This parameter is used to set the direction and speed of the PG input terminals
when the PG terminal are used as the control input.
This parameter sets PG Point 2 Frequency and is the frequency that is
associated with the setting of PG Point 2 Setting.
See PG Point 1 Setting for further information on this setting.
Direct Access Number — F237
Parameter Type — Numerical
Factory Default — 60.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — Max. Freq. (
F011
)
Units — Hz
Start Frequency
Program
⇒
Special
⇒
Frequency Control
The output of the drive will remain at 0.0 Hz until the programmed speed value
exceeds this setting during startup. Once exceeded during startup, the output
frequency of the drive will accelerate to the programmed setting.
Output frequencies below the Start Frequency will not be output from the
drive during startup. However, once reaching the Start Frequency, speed
values below the Start Frequency may be output from the drive.
If the setting of this parameter results in an overcurrent condition at startup,
reduce the setting of this parameter to a value less than the rated slippage of the
motor.
If zero-speed torque is required, set this parameter and
F243
to 0.0 Hz.
This setting will override the setting of
F244
if this setting has a higher value.
This parameter setting is used during a Jog as the Lower Limit frequency (see
F260
).
Direct Access Number — F240
Parameter Type — Numerical
Factory Default — 0.10
Changeable During Run — Yes
Minimum — 0.00
Maximum — Max. Freq. (
F011
)
Units — Hz
Run Frequency
Program
⇒
Special
⇒
Frequency Control
This parameter establishes a center frequency (Run Frequency) of a frequency
band.
Parameter
F242
provides a plus-or-minus value for the Run Frequency; thus,
establishing a frequency band.
During acceleration, the drive will not output a signal to the motor until the
lower level of the band is reached.
During deceleration, the drive will continue to output the programmed
deceleration signal to the motor until the lower level of the band is reached; at
which time the output will go to 0.0 Hz.
Direct Access Number — F241
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — Max. Freq. (
F011
)
Units — Hz
F236
F241