114
H9 ASD Installation and Operation Manual
RX Input Point 2 Setting
Program
⇒
Frequency
⇒
Speed Reference Setpoints
This parameter is used to set the gain and bias of the RX input terminal when
the RX terminal is used as the control input while operating in the Speed
Control mode or the Torque Control mode.
This parameter sets the RX input level that is associated with RX Input Point 2
Frequency
when operating in the Speed control mode or is associated with the
RX Input Point 2 Rate when operating in the Torque Control mode.
This value is entered as -100% to +100% of the RX input signal range.
See RX Input Point 1 Setting for more information on this setting when used
for Speed control.
See RX Input Point 1 Rate for more information on this setting when used for
Torque Control.
Direct Access Number — F218
Parameter Type — Numerical
Factory Default — +100
Changeable During Run — Yes
Minimum — -100.0
Maximum — +100.0
Units — %
RX Input Point 2 Frequency
Program
⇒
Frequency
⇒
Speed Reference Setpoints
This parameter is used to set the gain and bias of the RX input terminal when
the RX terminal is used as the control input while operating in the Speed
Control mode.
This parameter sets RX Input Point 2 Frequency and is the frequency that is
associated with the setting of RX Input Point 2 Setting when operating in the
Speed Control mode.
See RX Input Point 1 Setting for more information on this setting.
Direct Access Number — F219
Parameter Type — Numerical
Factory Default — 60.00
Changeable During Run — Yes
Minimum — 0.00.
Maximum — Max. Freq. (
F011
)
Units — Hz
F218
F219