8.1 Outline of Operation
Unified Controller nv Series FL-net Remote I/O Station Module FL654A User's Manual
53
8
8.1.2 Allocation of G2 I/O Module Data to Common Memory
When FL654A operates by "TOOL specification", FL654A subordinate's G2 I/O module data is
allocated to FL-net common memory as follows.
(1) Input module data can be allocated freely to FL654A talker area by each input module. FL654A
talker area can be allocated in both area1 and area2 in FL-net common memory.
(2) Output module data can be allocated freely to the areas other than FL654A talker area by each
output module.
Table 8-1 Difference of TOOL specification and AUTO / LOCK specification
Item
AUTO / LOCK specification
TOOL specification
Input module data
Allocation
Input module data is allocated from
the head of talker block in the former
stuff.
Talker block head address is
specified with rotary switch
(TBH,TBL).
Input module data can be allocated
freely to FL654A talker area by each
input module.
(Talker block setting of nV-Tool is
used.)
Output module data
Allocation
Output module data is allocated
from the head of listener block in the
former stuff.
Listener block head address is
specified with rotary switch
(LBH,LBL).
Output module data can be allocated
freely to the areas other than FL654A
talker area.
(Talker block setting of nV-Tool is
used.)
Send data allocation
area
(Talker block)
Send data allocation area can set
one consecutive area to either of
FL-net common memory area1 or
area2 at the same time.
Rotary switch (TBH,TBL) is not used.
FL654A talker area becomes send
data allocation area.
One consecutive
send data
allocation area can be set
respectively of common memory
area1 and area2.
Receive data
allocation area
(Listener block)
Receive data allocation area can set
one consecutive area to either of
common memory area 1 or area 2 at
the same time.
Rotary switch (LBH,LBL) is not used.
Because data in FL-net common
memory other than FL654A talker
area can be specified for receive
data allocation area.
Area1 block head
address / size
Block head address: 2 word unit
Size: 2 word unit
Block head address: 1 word unit
Size: 1 word unit
Area2 block head
address / size
Block head address: 32 word unit
Size: 32 word unit
Block head address: 1 word unit
Size: 1 word unit
Status information of
I/O module and
FL654A healthy counter
It is allocated to first 4 words of send
data allocation area.
It is allocated to first 4 words of send
data allocation area.
Summary of Contents for FL654A
Page 1: ...Unified Controller nv Series FL net Remote I O Station Module FL654A User s Manual 6F8C1625 ...
Page 16: ...6F8C1625 xiv ...
Page 38: ...Chapter 3 System Construction 6F8C1625 22 3 ...
Page 48: ...Chapter 5 I O configuration information 6F8C1625 32 5 ...
Page 88: ...Chapter 8 Startup Using nV Tool 6F8C1625 72 8 ...
Page 98: ...Chapter 9 Maintenance Using nV Tool 6F8C1625 82 9 ...
Page 105: ...B 89 Appendix B Outside Dimensions ...
Page 107: ...C 91 Appendix C Accessories and Related Products C 1 Accessories 92 C 2 Related Products 93 ...
Page 110: ...Appendix C Accessories and Related Products 6F8C1625 94 C ...
Page 111: ...D 95 Appendix D Decimal hexadecimal Conversion Table ...
Page 114: ...Appendix D Decimal hexadecimal Conversion Table 6F8C1625 98 D ...
Page 116: ...1625 1 1810 ...