Chapter 2 Hardware
6F8C1625
12
2
2.9 Talker Block Head/Listener Block Head Setting Switches
(TBH, TBL, LBH, and LBL)
↑
↑
↑
↑
TBH TBL LBH LBL
Figure 2-9 Talker Block Head/Listener Block Head Setting Switches
These switches set the head addresses of the FL654A talker area and listener area in the FL-net
cyclic common memory. They are hexadecimal rotary switches, and are located in the lower left side
face of the module when facing the module. The switches are set using a small flat-head screwdriver.
Because the settings are read at power-ON of the FL654A, if you wish to change a setting, turn OFF
the power, change the setting, and then turn ON the power again.
The FL654A stores data read from the input modules, starting at the head address of the talker area
set using the talker block head setting switch. It periodically sends data in cyclic transmission.
In contrary, the FL654A reads data starting at the head address of the listener area set using the
listener block head setting switch. It outputs data to the output modules.
The switches set the numbers of blocks that are formed by dividing Area 1 (512 words) or Area 2 (8K
words) of the FL-net cyclic transmission common memory into 256 blocks. The block numbers
range front 0 to FFh, and the high-order digits are set in “**H” and the low-order digits are set in “**L.”
Area 1: one block = 2 words (512 words / 256 = 2 words)
Area 2: one block = 32 words (8192 words / 256 = 32 words)
Table 2-6 Setting the Talker and Listener Blocks
Switch Name
Setting Description
Setting at Factory
default
TBH
High-order digits of talker block head number
0
TBL
Low-order digits of talker block head number
0
LBH
High-order digits of listener block head number
0
LBL
Low-order digits of listener block head number
0
Summary of Contents for FL654A
Page 1: ...Unified Controller nv Series FL net Remote I O Station Module FL654A User s Manual 6F8C1625 ...
Page 16: ...6F8C1625 xiv ...
Page 38: ...Chapter 3 System Construction 6F8C1625 22 3 ...
Page 48: ...Chapter 5 I O configuration information 6F8C1625 32 5 ...
Page 88: ...Chapter 8 Startup Using nV Tool 6F8C1625 72 8 ...
Page 98: ...Chapter 9 Maintenance Using nV Tool 6F8C1625 82 9 ...
Page 105: ...B 89 Appendix B Outside Dimensions ...
Page 107: ...C 91 Appendix C Accessories and Related Products C 1 Accessories 92 C 2 Related Products 93 ...
Page 110: ...Appendix C Accessories and Related Products 6F8C1625 94 C ...
Page 111: ...D 95 Appendix D Decimal hexadecimal Conversion Table ...
Page 114: ...Appendix D Decimal hexadecimal Conversion Table 6F8C1625 98 D ...
Page 116: ...1625 1 1810 ...