8.2 Remote I/O Startup Procedure
Unified Controller nv Series FL-net Remote I/O Station Module FL654A User's Manual
61
8
(3) FL654A module parameter setting
IP address, the first address and the amount of transmission words of area1, the first
address and the amount of transmission words of area2 are set at this stage. Because it
needs it in "
6 Registering the talker blocks
".
The amount of the transmission word in area 1 and area 2 is the values in which the amount
of the input module word and the I/O module status information (four words) were added.
(4) Create the dummy station for the remote station.
The dummy station needs to be registered to use data that send from FL622 in remote I/O
station.
Example:
(i) Register dummy station “oth_stn1(other station)”
(ii) Register “FLStn” as unit and “FL_Y” as module
Registration of dummy station
Summary of Contents for FL654A
Page 1: ...Unified Controller nv Series FL net Remote I O Station Module FL654A User s Manual 6F8C1625 ...
Page 16: ...6F8C1625 xiv ...
Page 38: ...Chapter 3 System Construction 6F8C1625 22 3 ...
Page 48: ...Chapter 5 I O configuration information 6F8C1625 32 5 ...
Page 88: ...Chapter 8 Startup Using nV Tool 6F8C1625 72 8 ...
Page 98: ...Chapter 9 Maintenance Using nV Tool 6F8C1625 82 9 ...
Page 105: ...B 89 Appendix B Outside Dimensions ...
Page 107: ...C 91 Appendix C Accessories and Related Products C 1 Accessories 92 C 2 Related Products 93 ...
Page 110: ...Appendix C Accessories and Related Products 6F8C1625 94 C ...
Page 111: ...D 95 Appendix D Decimal hexadecimal Conversion Table ...
Page 114: ...Appendix D Decimal hexadecimal Conversion Table 6F8C1625 98 D ...
Page 116: ...1625 1 1810 ...