Chapter 8 Startup Using nV-Tool
6F8C1625
64
8
6
Registering the talker blocks
Talker blocks are registered on "Scanning memory folder" of "FL-net Control LAN".
Talker block of the dummy station for the remote I/O station and talker block of FL654A are
registered respectively.
Talker block of dummy station for remote I/O station
Talker block of dummy station for remote I/O station is set to the place of FL-net
common memory area allocated in FL654A subordinate's output module.
In this sample, it registers thoroughly to talker block of FL622 of "FL-net LAN".
Talker block of FL654A
Word No. of talker block for FL654A talker area must be set "head address of
FL654A talker area +4words”. These 4words have been reserved for RAS data
such as healthy counters of FL654A.
When the above-mentioned rule is not observed, the download of I/O
configuration information becomes an error (text parameter error).
In this sample, word No. of talker block is made "head address of talker area
+4words".
Word No. of talker block for FL654A talker area must be set
"head address of FL654A talker area +4words”.
Area2 talker area head address is 512 …”516”
Summary of Contents for FL654A
Page 1: ...Unified Controller nv Series FL net Remote I O Station Module FL654A User s Manual 6F8C1625 ...
Page 16: ...6F8C1625 xiv ...
Page 38: ...Chapter 3 System Construction 6F8C1625 22 3 ...
Page 48: ...Chapter 5 I O configuration information 6F8C1625 32 5 ...
Page 88: ...Chapter 8 Startup Using nV Tool 6F8C1625 72 8 ...
Page 98: ...Chapter 9 Maintenance Using nV Tool 6F8C1625 82 9 ...
Page 105: ...B 89 Appendix B Outside Dimensions ...
Page 107: ...C 91 Appendix C Accessories and Related Products C 1 Accessories 92 C 2 Related Products 93 ...
Page 110: ...Appendix C Accessories and Related Products 6F8C1625 94 C ...
Page 111: ...D 95 Appendix D Decimal hexadecimal Conversion Table ...
Page 114: ...Appendix D Decimal hexadecimal Conversion Table 6F8C1625 98 D ...
Page 116: ...1625 1 1810 ...