2
Equipment selection procedure
9
2-2. Combination conditions for indoor unit and
outdoor unit
2-2-1. The capacity code for indoor unit, the capacity code is decided for each capacity rank.
2-2-2. The capacity codes of outdoor units are decided at each capacity type. The maximum number of connectable
indoor units and the total value of capacity codes of the indoor units are also decided.
NOTE
Compared with the capacity code of the outdoor unit, the total value of capacity codes of the connectable indoor
units differs based on the height difference between the indoor units.
When the height difference between the indoor units is 49 ft (15 m) or less
If “Medium Static Ducted Type (MMD-AP***BH)” is excluded in the system: Total indoor capacity code must be
between 80% and 125% of the capacity of the outdoor unit.
Total indoor capacity code must be between 80% and 120% of the capacity of the outdoor unit.
If “one of 007, 009 or 012 of 4-way Air Discharge Cassette type (MMU-AP***H*)” is included in the system:
Total indoor capacity code must be 80% - 105%.
When the height difference between the indoor units is over 49 ft (15 m)
Total indoor unit capacity code (Equivalent to Capacity) must be between 80% and 105% of the capacity of the
outdoor unit.
If “one of 007, 009 or 012 of 4-way Air Discharge Cassette type (MMU-AP***H*)” is included in the system:
Total indoor capacity code must be 80% - 105%.
Capacity rank type
007 009 012 015 018 021 024 027 030 036 042 048 054 072 096
Capacity code
(Equivalent to capacity)
7.5
9.5
12 15.4 18
21
24
27
30
36
42
48
54
72
96
System Outdoor unit
capacity
type
Outdoor
capacity code
(Equivalent to
capacity)
Maximum number of indoor units
If “Medium Static Ducted Type
(MMD-AP***BH)” is excluded in
the system
If “Medium Static Ducted Type
(MMD-AP***BH)” is included in
the system
Height difference between
indoor units
Height difference between
indoor units
49 ft (15 m) or
less
Over 49 ft (15 m) 49 ft (15 m) or
less
Over 49 ft (15 m)
Heat
recovery
072 type
72
12
10
11
10
096 type
96
16
13
15
13
120 type
120
20
16
19
16
144 type
144
24
20
23
20
168 type
168
28
23
26
23
192 type
192
32
26
30
26
216 type
216
36
30
34
30
240 type
240
40
33
38
33
288 type
288
48
40
46
40
312 type
312
48
43
48
43
336 type
336
48
47
48
47
Heat
pump
072 type
72
12
10
11
10
096 type
96
16
13
15
13
114 type
114
19
15
18
15
144 type
144
24
20
23
20
168 type
168
28
23
26
23
192 type
192
32
26
30
26
228 type
228
38
31
36
31
Summary of Contents for Carrier MMC-AP0181H2UL
Page 61: ...5 Outdoor unit 60 Model MMY MAP0964HT9UL MAP0964HT6UL MMY MAP1144HT9UL MAP1144HT6UL 72 9 ...
Page 76: ...5 Outdoor unit 75 Model MMY MAP0724FT6UL 460 V 60 Hz WHI WHI WHI PUR ...
Page 77: ...5 Outdoor unit 76 Model MMY MAP0964FT9UL MAP1204FT9UL 208 230 V 60 Hz ...
Page 78: ...5 Outdoor unit 77 Model MMY MAP0964FT6UL MAP1204FT6UL 460 V 60 Hz WHI WHI WHI PUR ...
Page 79: ...5 Outdoor unit 78 5 6 2 Heat pump Model MMY MAP0724HT9UL ...
Page 80: ...5 Outdoor unit 79 Model MMY MAP0724HT6UL ...
Page 81: ...5 Outdoor unit 80 Model MMY MAP0964HT9UL MAP1144HT9UL ...
Page 82: ...5 Outdoor unit 81 Model MMY MAP0964HT6UL MAP1144HT6UL ...
Page 212: ...MEMO ...
Page 213: ...Engineering Data Book For North America August 2015 First Edition ...