6
Indoor unit
184
6.
Electrical current characteristics
MCA: Minimum Circuit Amps FLA: Full Load Amps
MOCP: Maximum Overcurrent Protection (Amps)
Type
Model
Nominal Voltage
(V-Ph-Hz)
Voltage Range
(V)
Power
consumption
FLA
MCA MOCP
Min
Max
kW
A
A
A
High
Static
Ducted
type
MMD-AP0304H2UL
208/230-1-60
187
253
0.38/0.41
2.34
2.93
15
MMD-AP0364H2UL
208/230-1-60
187
253
0.38/0.41
2.34
2.93
15
MMD-AP0484H2UL
208/230-1-60
187
253
0.35/0.41
2.92
3.65
15
MMD-AP0724H2UL
208/230-1-60
187
253
1.37/1.44
7.12
8.91
15
MMD-AP0964H2UL
208/230-1-60
187
253
1.20/1.63
8.34
10.43
15