5-9. Optional PCB of outdoor unit
Model
name
Appearance
Function
TCB-
PCDM
4UL
Size: 2.80 × 3.35 (in)
Power peak-cut Control
Application
* Install the optional
PCB in the inverter
assembly of the
outdoor header unit.
Standard Specifications
(Wiring example)
<SW07 (bit 2) OFF [2-stage switching]>
Input
SW07 (bit 1)
Display relay
(L1)
SW1
SW2
Bit 1 OFF
Bit 1 ON
OFF
ON
100% (normal
operation)
100% (normal
operation)
OFF
ON
OFF
0% (forced stop)
Approx. 60% (upper
limit regulated)
ON
PJ17
CN513
SW07
TB1
[ON]
[OFF]
TB2
COM
ON
COM
OFF
Bit 2 OFF
L1
SW1
SW2
SW2
SW 1
ON
OFF
1 2 3 4
Outdoor unit
interface PCB
Connection cable (attached in this optional PCB)
Locally procured
Power
supply
[OPERATION]
L1: Display lamp during power peak cut control
Optional PCB
Header outdoor unit
Display
relay
Shield
wire
Shield
wire
For SW1 and SW2, be sure to provide no-voltage
contacts for each terminal.
The input signals of SW1 and SW2 may be pulse
input (100 msec or more) or continuous make.
Do not turn on [SW1] and [SW2] simultaneously.
For one input function
<SW07 (bit 2) OFF [2-stage switching]>
Jumper
lead J16
Input
SW1
SW07 (bit 1)
Display relay
(L1)
Bit 1 OFF
Bit 1 ON
Cut
OFF
100% (normal
operation)
100% (normal
operation)
OFF
ON
0% (forced stop)
Approx. 60%
(upper limit
regulated)
ON
PJ17
TB1
TB2
COM
ON
COM
OFF
CN513
SW07
Bit 2 ON
L1
SW 1
ON
OFF
1 2 3 4
[ON]
[OFF]
Outdoor unit
interface PCB
Connection cable (attached in this optional PCB)
Locally procured
Power
supply
[OPERATION]
L1: Display lamp during power peak cut control
Optional PCB
Header outdoor unit
Display
relay
J16 Cut
Shield
wire
Shield
wire
Power peak-cut ON-OFF control is made possible on the SHRM-i on
only the [ON] terminal input (SW1) by cutting the jumper lead (J16) of the
center outdoor unit interface PCB.
(Wiring example)
Power peak-cut control turns ON when SW1 in the wiring example is ON
(continuous make).
Summary of Contents for Carrier MMC-AP0181H2UL
Page 61: ...5 Outdoor unit 60 Model MMY MAP0964HT9UL MAP0964HT6UL MMY MAP1144HT9UL MAP1144HT6UL 72 9 ...
Page 76: ...5 Outdoor unit 75 Model MMY MAP0724FT6UL 460 V 60 Hz WHI WHI WHI PUR ...
Page 77: ...5 Outdoor unit 76 Model MMY MAP0964FT9UL MAP1204FT9UL 208 230 V 60 Hz ...
Page 78: ...5 Outdoor unit 77 Model MMY MAP0964FT6UL MAP1204FT6UL 460 V 60 Hz WHI WHI WHI PUR ...
Page 79: ...5 Outdoor unit 78 5 6 2 Heat pump Model MMY MAP0724HT9UL ...
Page 80: ...5 Outdoor unit 79 Model MMY MAP0724HT6UL ...
Page 81: ...5 Outdoor unit 80 Model MMY MAP0964HT9UL MAP1144HT9UL ...
Page 82: ...5 Outdoor unit 81 Model MMY MAP0964HT6UL MAP1144HT6UL ...
Page 212: ...MEMO ...
Page 213: ...Engineering Data Book For North America August 2015 First Edition ...