5
Outdoor unit
82
5-7. Connecting diagram
5-7-1. Heat recovery
5-7-2. Heat pump
Outdoor unit (Follower unit)
Outdoor unit (Header unit)
Indoor unit
Flow selector unit (FS unit)
Remote control
Central remote control (option)
Circuit breaker
Disconnect switch per NEC
W1 : Shielded control wiring between indoor and outdoor units
W2 : Shielded control wiring between indoor units
W3 : Shielded control wiring between outdoor units
W4 : Shielded central control wiring
3
㹼
60 Hz 208/230 V
3
㹼
60 Hz 460 V
Outdoor unit
power supply
Open
W3
W1
W2
Indoor unit
power supply
1
㹼
60 Hz 208/230 V
Central control
power supply
1
㹼
60 Hz 120 V
(Note)
1. When using a central control, plug in the connector between [U1,U2] and [U3,U4] terminal of the header
unit.
2. Connect the shield of all control wiring to the control ground screw on every unit. (Indoor & Outdoor)
3. Group control.
4. Power supply wiring to be per NEC and local codes.
5. For the control wires connecting indoor units, outdoor units, and between indoor and outdoor units, use 2-
core shielded wires.
6. For additional details, see the individual unit wiring diagrams. (Indoor & Outdoor)
7. Control wire and power line wire between FS unit and indoor unit are the accessory parts of FS unit.
(Wire length: 20 ft (6 m)
If the length between indoor and FS unit exceeds 16 ft (5 m), connect by using the connection cable kit sold
separately (RBC-CBK15FUL)
Connect the connector of control wiring on the indoor P.C. board, and so as the power supply wire to L and
N terminals.
8. When connecting the multiple indoor units to a single FS unit, only group control is available.
For the indoor unit, a remote control cannot be individually connected.
3
㹼
60 Hz 208/230 V
3
㹼
60 Hz 460 V
Outdoor unit
power supply
Summary of Contents for Carrier MMC-AP0181H2UL
Page 61: ...5 Outdoor unit 60 Model MMY MAP0964HT9UL MAP0964HT6UL MMY MAP1144HT9UL MAP1144HT6UL 72 9 ...
Page 76: ...5 Outdoor unit 75 Model MMY MAP0724FT6UL 460 V 60 Hz WHI WHI WHI PUR ...
Page 77: ...5 Outdoor unit 76 Model MMY MAP0964FT9UL MAP1204FT9UL 208 230 V 60 Hz ...
Page 78: ...5 Outdoor unit 77 Model MMY MAP0964FT6UL MAP1204FT6UL 460 V 60 Hz WHI WHI WHI PUR ...
Page 79: ...5 Outdoor unit 78 5 6 2 Heat pump Model MMY MAP0724HT9UL ...
Page 80: ...5 Outdoor unit 79 Model MMY MAP0724HT6UL ...
Page 81: ...5 Outdoor unit 80 Model MMY MAP0964HT9UL MAP1144HT9UL ...
Page 82: ...5 Outdoor unit 81 Model MMY MAP0964HT6UL MAP1144HT6UL ...
Page 212: ...MEMO ...
Page 213: ...Engineering Data Book For North America August 2015 First Edition ...