5
Outdoor unit
87
Model
name
Appearance
Function
TCB-
PCDM
4UL
Size: 2.80 × 3.35 (in)
Application
* Install the optional
PCB in the inverter
assembly of the
outdoor header unit.
Enhanced Specifications
(Wiring example)
<SW07 (bit 2) ON [4-stage switching]>
Input
SW07 (bit 1)
Display relay
(L1)
SW1
SW2
Bit 1 OFF
Bit 1 ON
OFF
OFF
100% (normal
operation)
100% (normal
operation)
OFF
ON
OFF
Approx. 80% (upper
limit regulated)
Approx. 85% (upper
limit regulated)
ON
OFF
ON
Approx. 60% (upper
limit regulated)
Approx. 75% (upper
limit regulated)
ON
ON
ON
0% (forced stop)
Approx. 60% (upper
limit regulated)
ON
PJ17
TB1
[ON]
[OFF]
TB2
COM
ON
COM
OFF
CN513
SW07
Bit 2 ON
L1
SW 1
ON
OFF
1 2 3 4
SW 2
Outdoor unit
interface PCB
Connection cable (attached in this optional PCB)
Locally procured
Power
supply
[OPERATION]
L1: Display lamp during power peak cut control
Optional PCB
Header outdoor unit
Display
relay
Shield
wire
Shield
wire
For SW1 and SW2, be sure to
provide no-voltage contacts for
each terminal.
Summary of Contents for Carrier MMC-AP0181H2UL
Page 61: ...5 Outdoor unit 60 Model MMY MAP0964HT9UL MAP0964HT6UL MMY MAP1144HT9UL MAP1144HT6UL 72 9 ...
Page 76: ...5 Outdoor unit 75 Model MMY MAP0724FT6UL 460 V 60 Hz WHI WHI WHI PUR ...
Page 77: ...5 Outdoor unit 76 Model MMY MAP0964FT9UL MAP1204FT9UL 208 230 V 60 Hz ...
Page 78: ...5 Outdoor unit 77 Model MMY MAP0964FT6UL MAP1204FT6UL 460 V 60 Hz WHI WHI WHI PUR ...
Page 79: ...5 Outdoor unit 78 5 6 2 Heat pump Model MMY MAP0724HT9UL ...
Page 80: ...5 Outdoor unit 79 Model MMY MAP0724HT6UL ...
Page 81: ...5 Outdoor unit 80 Model MMY MAP0964HT9UL MAP1144HT9UL ...
Page 82: ...5 Outdoor unit 81 Model MMY MAP0964HT6UL MAP1144HT6UL ...
Page 212: ...MEMO ...
Page 213: ...Engineering Data Book For North America August 2015 First Edition ...