(2) Indoor unit setup method for priority indoor unit mode
The setting can be changed only when the system is at rest. (Be sure to turn
off the system prior to this operation.)
1
Push the
+
+
buttons simultaneously and hold for at least
4 seconds. The display window will start flashing in a little while.
Verify that the displayed CODE No. is 10.
• If the displayed CODE No. is not 10, press the
button to erase the
display and repeat the procedure from the beginning.
(Note that the system does not respond to remote control operation for
about 1 minute after the
button is pushed.)
(In the case of group control, the indoor unit No. displayed first indicates
the header unit.)
2
Each time the
button is pushed, one of the indoor
unit Nos. under group control is displayed in turn. Select
the indoor unit whose setting is to be changed.
The fan and louver of the selected indoor unit then come on, so
that the position of this unit can be confirmed.
3
Use the
button to select the CODE No. 04.
4
Use the
button to select the SET DATA 0001.
Priority set 0001
No priority set 0000
5
Push the
button.
The setup is finished when the display changes from flashing to steady.
6
Upon finishing the setup, push the
button. (This
finalizes the setting.)
When the
button is pushed, the display goes blank, and the
system returns to normal off state.
(Note that the system does not respond to remote control
operation for about 1 minute after the
button is pushed.)
NOTE
Priority can be given to only one indoor unit. If more than one indoor unit is accidentally set to priority, an error code
(L5 or L6: Duplicated indoor unit priority setting) will be displayed.
All units displaying L5 have been set to 0001 (priority). Keep the unit to which priority should be given as it is, and
change the value back to 0000 (no priority) for all the rest.
Error code
Description
Duplicated indoor unit priority setting (The unit is set to 0001.)
Duplicated indoor unit priority setting (The unit is set to 0000.)
SET
TIME
TIMER SET
TEST
FILTER
RESET
TEMP.
CL
FAN
SAVE
SWING/FIX
VENT
MODE
ON / OFF
UNIT LOUVER
5
4
1
2
6
3
UNIT LOUVER
Summary of Contents for Carrier MMC-AP0181H2UL
Page 61: ...5 Outdoor unit 60 Model MMY MAP0964HT9UL MAP0964HT6UL MMY MAP1144HT9UL MAP1144HT6UL 72 9 ...
Page 76: ...5 Outdoor unit 75 Model MMY MAP0724FT6UL 460 V 60 Hz WHI WHI WHI PUR ...
Page 77: ...5 Outdoor unit 76 Model MMY MAP0964FT9UL MAP1204FT9UL 208 230 V 60 Hz ...
Page 78: ...5 Outdoor unit 77 Model MMY MAP0964FT6UL MAP1204FT6UL 460 V 60 Hz WHI WHI WHI PUR ...
Page 79: ...5 Outdoor unit 78 5 6 2 Heat pump Model MMY MAP0724HT9UL ...
Page 80: ...5 Outdoor unit 79 Model MMY MAP0724HT6UL ...
Page 81: ...5 Outdoor unit 80 Model MMY MAP0964HT9UL MAP1144HT9UL ...
Page 82: ...5 Outdoor unit 81 Model MMY MAP0964HT6UL MAP1144HT6UL ...
Page 212: ...MEMO ...
Page 213: ...Engineering Data Book For North America August 2015 First Edition ...