5
Outdoor unit
57
5-2-1-2. Combination
keep 19.7" in (500 mm) or more between the outdoor unit and traversing pipe if placing pipe
3. Draw out the pipe procured locally to the front of the outdoor unit horizontally, and
the bottom end of the outdoor unit.
2. Limit the height of the obstacle surrounding the outdoor unit to 31.5" in (800 mm) or less from
unit 78.7" in (2000 mm) apart from the obstacle.
1. If there is an obstacle at the upper side of the outdoor unit, set the top end of the outdoor
transversely.
(Note)
(Header unit Follower unit )
2
>
_
1
4. Arrange each outdoor unit in order of its capacity.
_ >
h
31.5"(800)
7.87"(200)
19.7"(500)
23.6"(600)
0.39"(10)
86.6"(2200)
70.1"(1780)
39.4"(1000)
>
_
c
>
e
f
g
_
>
_
>
d
_
_
>
>
_
a
b
_
>
(4-15×20)
(Anchor bolt hole pitch)
(Anchor bolt hole pitch)
(Anchor bolt hole pitch)
(Including steady leg)
(Long hole)
(200)
7.87" or more
4-0.59"×0.79"
or more
19.3"
(490)
39.0"(990)
27.6"(700)
27.6"(700)
39.0"(990)
29.7"(755)
30.7"(780)
31.1"(790)
1.97"(50)
72.9"(1850)
3.35"(85)
62.8"(1595)
27.0"(687)
1.97"(50)
Two units connected
Outdoor unit
Header unit
Model name
MMY-AP1444FT9UL
MMY-MAP0724FT9UL
MMY-MAP0724FT9UL
Follower unit
MMY-MAP0724FT6UL
MMY-MAP0724FT6UL
MMY-AP1444FT6UL
(Unit:in (mm))
a
a
e
f
e
d
c
Space required for service
Front side
(For work and service)
a
b
b
a
e
f
( g )
(Note 3)
Front side
Front side
Front side
Front side
Front side
Front side
a
b
( g )
(Note 3)
a
a
a
e
f
e
f
h
Front side
Front side
Front side
Front side
Front side
Front side
_ >
h
31.5"(800)
7.87"(200)
19.7"(500)
23.6"(600)
0.39"(10)
95.3"(2420)
70.1"(1780)
39.4"(1000)
>
_
c
>
e
f
g
_
>
_
>
d
_
_
>
>
_
a
b
_
>
29.7"(755)
30.7"(780)
31.1"(790)
36.2"(920)
27.6"(700)
47.6"(1210)
39.0"(990)
(Including steady leg)
(Anchor bolt hole pitch)
(Long hole)
(4-15×20)
(Anchor bolt hole pitch)
(Anchor bolt hole pitch)
(490)
(200)
7.87" or more
19.3" or more
4-0.59"×0.79"
72.9"(1850)
3.35"(85)
27.0"(687)
62.8"(1595)
1.97"(50)
1.97"(50)
Outdoor unit
Header unit
Model name
MMY-AP1684FT9UL MMY-MAP0964FT9UL
MMY-MAP0724FT9UL
Follower unit
MMY-AP1684FT6UL MMY-MAP0964FT6UL
MMY-MAP0724FT6UL
Two units connected
keep 19.7" in (500 mm) or more between the outdoor unit and traversing pipe if placing pipe
3. Draw out the pipe procured locally to the front of the outdoor unit horizontally, and
the bottom end of the outdoor unit.
2. Limit the height of the obstacle surrounding the outdoor unit to 31.5" in (800 mm) or less from
unit 78.7" in (2000 mm) apart from the obstacle.
1. If there is an obstacle at the upper side of the outdoor unit, set the top end of the outdoor
transversely.
(Note)
4. Arrange each outdoor unit in order of its capacity.
2
>
_
1
(Header unit Follower unit )
(Unit:in (mm))
( g )
(Note 3)
a
ba
a
a
f
e
e
f
h
Front side
Front side
Front side
Front side
Front side
Front side
a
a
d
e
f
c
e
Space required for service
(For work and service)
Front side
a
b
b
a
( g )
(Note 3)
e
f
Front side
Front side
Front side
Front side
Front side
Front side
Summary of Contents for Carrier MMC-AP0181H2UL
Page 61: ...5 Outdoor unit 60 Model MMY MAP0964HT9UL MAP0964HT6UL MMY MAP1144HT9UL MAP1144HT6UL 72 9 ...
Page 76: ...5 Outdoor unit 75 Model MMY MAP0724FT6UL 460 V 60 Hz WHI WHI WHI PUR ...
Page 77: ...5 Outdoor unit 76 Model MMY MAP0964FT9UL MAP1204FT9UL 208 230 V 60 Hz ...
Page 78: ...5 Outdoor unit 77 Model MMY MAP0964FT6UL MAP1204FT6UL 460 V 60 Hz WHI WHI WHI PUR ...
Page 79: ...5 Outdoor unit 78 5 6 2 Heat pump Model MMY MAP0724HT9UL ...
Page 80: ...5 Outdoor unit 79 Model MMY MAP0724HT6UL ...
Page 81: ...5 Outdoor unit 80 Model MMY MAP0964HT9UL MAP1144HT9UL ...
Page 82: ...5 Outdoor unit 81 Model MMY MAP0964HT6UL MAP1144HT6UL ...
Page 212: ...MEMO ...
Page 213: ...Engineering Data Book For North America August 2015 First Edition ...