User’s Manual
47
PART 2 DA264
5. I/O Allocation and Programming
0 to 10V range:
D/A conversion data
Hexadecimal
Integer
Output voltage
Resolution
Upper limit
H7F80
32640
+10.2 V
:
:
:
Full scale (positive)
H7D00
32000
+10 V
:
:
:
H0001
1
+0.3125 mV
0
H0000
0
0 V
0.3125 mV / bit
A = 0.3125
×
D
D: Digital data
A: Analog signal (mV)
H8000
-32768
0
H7FFF
32767
Analog output value
+10V
H7D00
32000
Digital data
Lower limit
CTi Automation - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: [email protected]