6F8C0845
95
4.5 Completion Status
4
4.5 Completion Status
The completion statuses that DN611 returns in response to the requests issued by the S
controller are shown below.
Except for normal completion, an error code and the local node address are alternately
indicated by the 7-segment LED on the front panel of the DN611.
The error code indication stops when the following request is completed normally.
Table 4-18 List of Completion Statuses
Completion status
Code
Description
Normal completion
0001H
Indicates a request is completed normally.
Local station failure 00A0H
When a request for inhibited processing is issued in down
mode
Serial number
unregistered
00A1H
A serial number registered in the DN611 disappeared
→
Ask
for repair because the DN611 needs resetting.
Local station
parameters not set
yet
00A2H
A request for inhibited processing is issued when local station
parameters have not been set yet.
Length error
00A3H
Data size of a bit strobe output data write request is 8 bytes or
more.
Station mode error
00A4H
A request for inhibited processing is issued during run mode; a
request for inhibited processing is issued during standby
mode.
00A5H
Reserved
Transmission
inhibited
00A6H
A request related to transmission is issued by the S controller
in a state where transmission is inhibited.
Format error
00B0H
Requested processing code is not supported
00B1H
Inhibited status is demanded by control request
00B2H
Requested year is invalid at time setting
00B3H
Requested month is incorrect at time setting
00B4H
Request day is incorrect at time setting
00B5H
Request hour is incorrect at time setting
00B6H
Request minute is incorrect at time setting
00B7H
Request second is incorrect at time setting
00B8H
Incorrect node address (other than 0 to 63) is set in response
to parameter setting request and explicit message request.
Component data
error
00C0H
Incorrect data is in the data constituting parameter setting
request. (See trace information for details.)
00C1H
Slave device input/output data cannot be allocated to the input/
output data area (when control request RUN is issued).
Memory pool
acquisition error
00C2H
The OS in the DN611 has failed to secure memory. Switch
power off and back on to reset the module.