58
model 2000 DeviceNet Module Manual (DN611/DN611A)
Chapter 4 Operating Procedures for the DN611 (Software)
4
4.2.2
RAS information area
This area shows the DN611's module status and status of communication with the
network and slave devices. Don't write data in this area. Otherwise, there is a possibility
of being unable to read the correct data. The addresses in Figure 4-10 are word
addresses as viewed from the S controller.
Figure 4-10 RAS Information Area Configuration
0107H
Network power unit yes/no (1 word)
0108H
Operation mode in case of busoff (1 word)
0109H
Network communication rate (1 word)
010AH
Local station node address (1 word)
010BH
Input/output data setting information (384 words)
028BH
Reserved (8 words)
0293H
Bit strobe no-response device (4 words)
0297H
Polling no-response device (4 words)
029BH
Number of polling devices (1 word)
029CH
Number of bit strobe devices (1 word)
029DH
Number of on-line devices (1 word)
029EH
Total number of devices (1 word)
029FH
Configuration information (32 words)
02BFH
Node error counter (7 words)
02C6H
Completion of module initialization (1 word)
02C7H
Reserved (1 word)
02C8H
Polling/Bit strobe scan cycle (5 words)
02CDH
Down information (1 word)
02CEH
Station status (1 word)