B-7
1600XP/XPi Series Installation and Operation Manual – 60616-012
206
Output
Active Power (W)
Output Power(W)
R
R
R
R
R
0
-1 if output active power can not be calculated (Bypass
Mode).
Units: W
207
Output
Apparent Power (V
A)
Output Power(V
A)
R
R
R
R
R
0
Units: V
A
209
Output Load Percentage
(T
otal)
Output Load (%)
R
R
R
R
R
0
Defined as output current percentage or output active
power whichever higher
.
Units: %
215
Rated Output V
oltage
(T
otal)
Rated V
out
R
R/W
R/W
R/W
R/W
240
Must be non-zero value. Undefined behavior if diveded
by zero.
Range: 1 – 300
Units: V
rms
216
Rated Output Current
(T
otal)
Rated Iout
R
R
R
R/W
R/W
250
Calculated from typeform and not writable.
Range: 0 – 1500
Units: 0.1
Arms
217
Rated Output Frequency
(T
otal)
Rated Fout
R
R
R
R
R
0
Determined according to DIP
switch or EEPROM setup.
Units: 0.1 Hz
218
Rated Output
Active Power
Rated Pout(W)
R
R
R
R
R
0
UPS calculates at the startup according to typeform,
efficiency and rated power factor
.
Units: W
219
Rated Output
Apparent Power
Rated Pout(V
A)
R
R
R
R
R
0
UPS calculates at the startup according to typeform,
efficiency and rated power factor
.
Units: V
A
220
Output Under V
oltage Fault
Detection Level
VOUV DeLevel
R
R
R
R/W
R/W
90
Output Under V
oltage Detection level in percentage of
Rated Output V
oltage.
Range: 0 – 100
Units: %
222
Output Overvoltage Fault
Level
VOOV DeLevel
R
R
R
R/W
R/W
11
0
Output Over V
oltage Detection level in percentage of
Rated Output V
oltage.
Range: 100 – 150
Units: %
224
Output Frequency
Synchronization Range
Fo Syn Window
R
R
R
R/W
R/W
10
Output voltage will follow input voltage if the dif
ference of
input and output are within this value (according to slew rate).
Range: 1 – 30
Units: 0.1 Hz
Item
Brief Description
Description
On LCD
U
A
D
Svc/ QC
F
Default
Remark
Summary of Contents for 1600XP SERIES
Page 2: ...b 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 6: ...f 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 10: ...iv 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 74: ...64 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 112: ...B 32 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 115: ...C3 1600XP XPi Series Installation and Operation Manual 60616 012 8 10 kVA Dimensions ...
Page 132: ...E2 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 139: ......