B-25
1600XP/XPi Series Installation and Operation Manual – 60616-012
657
Service Port Mode
Service Port Mode
-
-
-
R/W
R/W
1: Protocol Rqrd.
0:
Terminal mode (no handshake, no error check)
1:
Toshiba UPS Communication Protocol 2-0 mode
658
Enable Restart
(After Battery Shutdown)
En Restart
R
R/W
R/W
R/W
R/W
1: Enable
0: Disable
1: Enable
659
Restart Delay
(After Battery Shutdown)
Restart Delay
R
R/W
R/W
R/W
R/W
10 Sec
Range: 0 – 800
Units: Sec
660
Enable Auto
Transfer
(Current Limit)
En
AutoXfer
R
R/W
R/W
R/W
R/W
1: Enabled
0 = keep inverter
,
1 = go to bypass and come back to inverter after time delay CMD662
662
Auto ReT
ransfer Delay
(Current Limit)
AutoReXfer Window
R
R/W
R/W
R/W
R/W
3 Sec
Time period to wait after current limit occurrence before attempting tranfer back Online.
Range: 0 – 600
Units: Sec
663
Service Port Baud Rate Settings*
Srv Port Baud*
R
R/W
R/W
R/W
R/W
3
no hardware control, no parity
, 1 stop bit, 8 bits of data
and baud rate are (Restart Required)
0: 9600
1: 19200
2: 38400
3: 57600
680
All EEPROM Reload*
Reload
All EE*
-
-
-
R/W
R/W
0
0 = do nothing
1 = reload all EEPROM with ROM DEF
AUL
T
2 = reload CFG and STR types with ROM DEF
AUL
T
681
SNMP
Port Mode
SNMP
Port Mode
-
-
-
R/W
R/W
1: Protocol Rqrd.
0:
Terminal mode (no handshake, no error check)
1:
Toshiba UPS Communication Protocol 2-0 mode
682
Fault Clear counter
Flt Cleared Cnt
R
R
R
R/W
R/W
0
683
Fault Clear Mask Low
Flt Clear Mask Lo
-
-
-
R/W
R/W
0x0000
Range: 0x0000 – 0xFFFF
Units: Hex
684
Fault Clear Mask High
Flt Clear Mask Hi
-
-
-
R/W
R/W
0x0000
Range: 0x0000 – 0xFFFF
Units: Hex
685
Total
Faults Allowed
Total
Flt
Allowed
-
-
-
R/W
R/W
10
Range: 0 – 255
686
Fault
Disable
Time
Flt
Dis T
ime
-
-
-
R/W
R/W
10
Range: 0 – 255
Units: Min
687
Fault Disable Countdown Timer
Flt Dis Cdown
Tmr
R
R
R
R
R
0
Units: Sec
Item
Brief Description
Description
On LCD
U
A
D
Svc/ QC
F
Default
Remark
Summary of Contents for 1600XP SERIES
Page 2: ...b 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 6: ...f 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 10: ...iv 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 74: ...64 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 112: ...B 32 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 115: ...C3 1600XP XPi Series Installation and Operation Manual 60616 012 8 10 kVA Dimensions ...
Page 132: ...E2 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 139: ......