![Toshiba 1600XP SERIES Installation And Operation Manual Download Page 125](http://html.mh-extra.com/html/toshiba/1600xp-series/1600xp-series_installation-and-operation-manual_431528125.webp)
D9
1600XP/XPi Series Installation and Operation Manual – 60616-012
14kVA
–
UH3G2L140C61T / H3BG2L140C61T
(Runtimes are approximate)
UPS
ESTIMATED
RUNTIME WITH ONLY INTERNAL BATTERIES @ .70pf
Rating
PF
Output
Voltage
Rated I
Rated
Load %
Output
Watts
# Batt
# Strings Nominal
Runtime
14
0.7
240
58.33
0.10
980
24
2
288
135
14
0.7
240
58.33
0.20
1960
24
2
288
72
14
0.7
240
58.33
0.30
2940
24
2
288
50
14
0.7
240
58.33
0.40
3920
24
2
288
38
14
0.7
240
58.33
0.50
4900
24
2
288
28
14
0.7
240
58.33
0.60
5880
24
2
288
21
14
0.7
240
58.33
0.70
6860
24
2
288
17
14
0.7
240
58.33
0.80
7840
24
2
288
15
14
0.7
240
58.33
0.90
8820
24
2
288
12
14
0.7
240
58.33
1.00
9800
24
2
288
7
UPS
ESTIMATED
RUNTIME WITH INTERNAL BATTERIES AND 1 MATCHING BATTERY CABINET @ .70pf
Rating
PF
Output
Voltage
Rated I
Rated
Load %
Output
Watts
# Batt
# Strings Nominal
Runtime
14
0.7
240
58.33
0.10
980
24
5
288
300
14
0.7
240
58.33
0.20
1960
24
5
288
165
14
0.7
240
58.33
0.30
2940
24
5
288
120
14
0.7
240
58.33
0.40
3920
24
5
288
90
14
0.7
240
58.33
0.50
4900
24
5
288
82
14
0.7
240
58.33
0.60
5880
24
5
288
63
14
0.7
240
58.33
0.70
6860
24
5
288
55
14
0.7
240
58.33
0.80
7840
24
5
288
48
14
0.7
240
58.33
0.90
8820
24
5
288
43
14
0.7
240
58.33
1.00
9800
24
5
288
38
UPS
ESTIMATED
RUNTIME WITH INTERNAL BATTERIES AND 2 MATCHING BATTERY CABINETS @ .70pf
Rating
PF
Output
Voltage
Rated I
Rated
Load %
Output
Watts
# Batt
# Strings Nominal
Runtime
14
0.7
240
58.33
0.10
980
24
8
288
300
14
0.7
240
58.33
0.20
1960
24
8
288
300
14
0.7
240
58.33
0.30
2940
24
8
288
180
14
0.7
240
58.33
0.40
3920
24
8
288
135
14
0.7
240
58.33
0.50
4900
24
8
288
112
14
0.7
240
58.33
0.60
5880
24
8
288
98
14
0.7
240
58.33
0.70
6860
24
8
288
86
14
0.7
240
58.33
0.80
7840
24
8
288
78
14
0.7
240
58.33
0.90
8820
24
8
288
65
14
0.7
240
58.33
1.00
9800
24
8
288
60
Summary of Contents for 1600XP SERIES
Page 2: ...b 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 6: ...f 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 10: ...iv 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 74: ...64 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 112: ...B 32 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 115: ...C3 1600XP XPi Series Installation and Operation Manual 60616 012 8 10 kVA Dimensions ...
Page 132: ...E2 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 139: ......