27
1600XP/XPi Series Installation and Operation Manual – 60616-012
13.3 Status Indicators
The four top and three bottom UPS status Indicators on the main screen and their meanings are listed in
the table below.
Indicator
Functional Description
96%
Shows the current load percentage.
100% / 11’
100% / 9’ 35”
100% / N/A
Battery Information: In On-Line and Battery Back-up mode the display alternates between
battery charge percentage and estimated remaining battery runtime in:
Format
xx M – Minutes for Runtimes > 10 min.
xx M.xx S – Minutes and Seconds for Runtimes < 10 min.
In other modes, the display alternates between battery charge percentage and “N/A.”
INV
Shows current UPS Status. Indicator will change as the UPS status changes. For a
detailed listing see
12:35 PM
System Time
DVCOH
Fault Description Code – For a detailed listing see page 53
.
ASYN
Warning Description Code – For a detailed listing see page 54
.
On-Line
Current Operating Mode of the UPS – For a detailed listing see page 56
.
13.4 Light Emitting Diodes (LED)
The following table describes the front panel LED behaviors and the associated meaning.
LED
Behavior
Significance/Meaning
Green - ON
UPS is in On-Line, Backup, or Battery Test mode.
Green - OFF
UPS in Bypass mode.
Green - OFF
Load Discharging
Red - ON
One or more faults occurred. See
Records: Faults
for details.
Red - Flashing
Charger overvoltage occurred.
Red - OFF
No fault occurred.
Amber - ON
Service Call needed,
Less than 6 mo. of Battery Life
or
Battery Life
End
.
Amber - Flashing
One or more Warnings occurred. See
Records: Warnings
for details.
Amber - OFF
No Warning (Normal, UPS in operation).
Green - ON
Input voltage is within specified range.
Green - Flashing
Input voltage is over specified range.
Green - OFF
Input voltage is under specified range.
NOTE: On-Line/Fault LEDs - Appear Amber if Green and Red flash concurrently.
AC Input
Warning
On-Line/
Fault
Summary of Contents for 1600XP SERIES
Page 2: ...b 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 6: ...f 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 10: ...iv 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 74: ...64 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 112: ...B 32 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 115: ...C3 1600XP XPi Series Installation and Operation Manual 60616 012 8 10 kVA Dimensions ...
Page 132: ...E2 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 139: ......