B-21
1600XP/XPi Series Installation and Operation Manual – 60616-012
572-19
Constant V
oltage Mode
Charger Reference BC2
CV Mode Chg Ref
-
-
R
R/W
R/W
This parameter set current limit.
To increase current limit,
decrease reference.
This parameter af
fect only battery cabinet 2.
850 = ~ 3
Amp
Range: 540 – 1024
601
System T
emperature
Control PCB’
s I2C Device
System(CTL) Temp
R
R
R
R
R
0
Thermostat on control PCB.
Units: °C
602
Battery T
emperature
Battery
Temp
R
R
R
R
R
0
Thermistor attached to the case of battery tray
.
Units: °C
608
Current State of UPS
Current State
R
R
R
R
R
0: Shutdown [show Shutdown]
1: Initial Charge [show Shutdown]
2: Boostup [show Shutdown]
3: Normal (Online) [show Online]
4: Backup [show Backup]
5: Batttery
Test [show Battery
Test]
6: Bypass Normal [show Bypass]
7: Bypass Init [show Bypass]
8: Bypass Shutdown [show Bypass]
9: Startup [show Startup]
609
Operation
Mode T
ransition
State Requested
Requested State
R/W
R/W
R/W
R/W
R/W
1: Shutdown Request
2: Bypass Request
3: Online Request
4: Battery
Test Request
610
Operation
Mode T
ransition
Timer
Timed Operation
R/W
R/W
R/W
R/W
R/W
0 Sec
The timer upon whose expiration a mode transition will be attempted by the system.
Range: 0 – 800
Units: Sec
611
EPO Contact State
EPO Status
R
R
R
R
R
Report of EPO input contact status.
0: Open
1: Closed
612
UPS Faults
Faults
R/W
R/W
R/W
R/W
R/W
Only accept zero to clear Fault bit map
613
UPS W
arnings
W
arnings
R
R
R
R/W
R/W
Only accept zero to clear W
arning bit map
614
UPS System Status
UPS Status(Comm)
R
R
R
R
R
LSW is attached at every data package. See the details of bit map UX3FN19 (T
oshiba Communication Protocol
(TUCP
2.0) for external Reference.doc
Item
Brief Description
Description
On LCD
U
A
D
Svc/ QC
F
Default
Remark
Summary of Contents for 1600XP SERIES
Page 2: ...b 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 6: ...f 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 10: ...iv 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 74: ...64 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 112: ...B 32 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 115: ...C3 1600XP XPi Series Installation and Operation Manual 60616 012 8 10 kVA Dimensions ...
Page 132: ...E2 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 139: ......