B-22
1600XP/XPi Series Installation and Operation Manual – 60616-012
615
Run / Stop mechanical switch state
RunStop SW
Status
R
R
R
R
R
0: Stop
1: Run
617
Service Port Communication Status
SPort Status
R
R
R
R
R
0
0: Unknown
1: Normal & OK
2: Idle – Of
f (Disable)
3: Error
618
Internal Communication Status
Inter Comm Status
R
R
R
R
R
0
0: Unknown
1: Normal & OK
2: Idle or Of
f (Disable)
3: Error
619
Security Level Control
(Enter Password)
Security Level
R/W
R/W
R/W
R/W
R/W
Reading will give the current security level
USER
for User Level
ADMIN
for
Administration Level
DIST
for Distrubutor Level
QCNSR
V
for Qc and Service Level
ENG
for Engineering Level
NOTE:
Three communication chanels have their own
security level variables
620
Manage Admin
Password
Manage Admin
PW
-
R/W
R/W
R/W
R/W
ADMIN
Change
Admin
Password
621
Reset Admin
Password
Reset
Admin PW
R/W
R/W
R/W
R/W
R/W
0
0 = do nothing
1 = reset administration password
623
Bypass Enable*
En Bypass*
-
-
-
R/W
R/W
1: Enabled
DIP
Switch, EEPROM’
s Enable CVCF
, and this value
will decide the system’
s bypass availability (Restart
Required)
0: Disable
1: Enable
624
Enable
Transfer to Bypass
while in
Async mode
En Asyn
Byp
-
-
-
R/W
R/W
1: Enable
When Disabled, the UPS will not prevent transfers to
bypass mode during periods when the frequencies are out of synch.
0: Disable
1: Enable
625
Enable CVCF*
En CVCF*
-
-
-
R/W
R/W
Constant V
oltage, Constant Frequency Mode
(Restart Required)
0: Disable
1: Enable
Item
Brief Description
Description
On LCD
U
A
D
Svc/ QC
F
Default
Remark
Summary of Contents for 1600XP SERIES
Page 2: ...b 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 6: ...f 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 10: ...iv 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 74: ...64 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 112: ...B 32 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 115: ...C3 1600XP XPi Series Installation and Operation Manual 60616 012 8 10 kVA Dimensions ...
Page 132: ...E2 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 139: ......