B-14
1600XP/XPi Series Installation and Operation Manual – 60616-012
503
Battery Discharge Current
Discharge Current
R
R
R
R
R
0
valid only when discharging and zero for charged mode
Units: 0.1
Adc
504
Battery Capacity
Battery Capacity
R
R/W
R/W
R/W
R/W
0
Range: 0 – 150
Units: %
505
Battery Runtime
Battery Runtime
R
R
R
R
R
400
506
Battery Charger Status
Charger Status
R
R
R
R
R
0
0 = Normal Charging
1 = Preventive Charging
2 = Stop Charging
507
Number of Battery Discharges
Total Discharges
R
R/W
R/W
R/W
R/W
0
Increment when backup mode more than 10 Sec long
508
Calculated Battery Shutdown
Voltage
Cal Battery Vsd
R
R
R
R
R
Calculated from manufacturer
’s data sheet.
Units: Vdc
509
Battery Life Remaining
Batt Life Remain
R
R/W
R/W
R/W
R/W
43800
Range: 0 – 43800
Units: Hr
511
Internal Battery Rated Capacity
in Ampere-Hour
Rated
Ahr
R
R/W
R/W
R/W
R/W
9
Battery capacity
Ampere-Hour such as 7
AHr or 9
Ahr
.
Range: 1 – 15
Units: Ahr
512
Number Internal Battery Packs In Series String
No Batt(Series)
R
R/W
R/W
R/W
R/W
18
Range: 0 – 48
513
Number Internal Battery Strings in Parallel
No Batt(Paral)
R
R/W
R/W
R/W
R/W
1
Number of internal battery strings. 3.6-14kV
A=1,
18/22kV
A=2.
Range: 1 – 24
514
Battery Installation Date
Batt Ins Date
R
R/W
R/W
R/W
R/W
“20080101”
YYYYMMDD
516
Battery V
oltage Shutdown
Level
Batt SDown Level
R
R
R/W
R/W
R/W
79
Percentage of nominal battery voltage.
Range: 0 – 120 Units: %
522
1
Enable External Battery
Cabinet 1
Enable BC1
R
R/W
R/W
R/W
R/W
0
0: Disable
1: Enable
523
1
Enable External Battery
Cabinet 1
Enable BC2
R
R/W
R/W
R/W
R/W
0
0: Disable
1: Enable
524
External Batt Cabinet Installation Status
SbatEx
-
-
-
R/W
R/W
0
0: Uninvested
1: Installed
Item
Brief Description
Description
On LCD
U
A
D
Svc/ QC
F
Default
Remark
Summary of Contents for 1600XP SERIES
Page 2: ...b 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 6: ...f 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 10: ...iv 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 74: ...64 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 112: ...B 32 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 115: ...C3 1600XP XPi Series Installation and Operation Manual 60616 012 8 10 kVA Dimensions ...
Page 132: ...E2 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 139: ......