D1
1600XP/XPi Series Installation and Operation Manual – 60616-012
Appendix D: Battery Backup Tables (Internal & External Bat-
tery Cabinets)
3.6kVA
–
UH3G2L036C61T / H3BG2L036C61T
(Runtimes are approximate)
UPS ESTIMATED RUNTIME WITH ONLY INTERNAL BATTERIES @ .70pf
Rating
PF
Output
Voltage
Rated I
Rated
Load %
Output
Watts
# Batt
# Strings Nominal
Runtime
3.6
0.7
240
15.00
0.10
252
12
1
144
82
3.6
0.7
240
15.00
0.20
504
12
1
144
53
3.6
0.7
240
15.00
0.30
756
12
1
144
40
3.6
0.7
240
15.00
0.40
1008
12
1
144
29
3.6
0.7
240
15.00
0.50
1260
12
1
144
22
3.6
0.7
240
15.00
0.60
1512
12
1
144
18
3.6
0.7
240
15.00
0.70
1764
12
1
144
16
3.6
0.7
240
15.00
0.80
2016
12
1
144
12
3.6
0.7
240
15.00
0.90
2268
12
1
144
11
3.6
0.7
240
15.00
1.00
2520
12
1
144
7
UPS ESTIMATED RUNTIME WITH INTERNAL BATTERIES AND 1
MATCHING
BATTERY CABINET @ .70pf
Rating
PF
Output
Voltage
Rated I
Rated
Load %
Output
Watts
# Batt
# Strings Nominal
Runtime
3.6
0.7
240
15.00
0.10
252
12
4
144
240
3.6
0.7
240
15.00
0.20
504
12
4
144
165
3.6
0.7
240
15.00
0.30
756
12
4
144
135
3.6
0.7
240
15.00
0.40
1008
12
4
144
105
3.6
0.7
240
15.00
0.50
1260
12
4
144
90
3.6
0.7
240
15.00
0.60
1512
12
4
144
82
3.6
0.7
240
15.00
0.70
1764
12
4
144
72
3.6
0.7
240
15.00
0.80
2016
12
4
144
65
3.6
0.7
240
15.00
0.90
2268
12
4
144
57
3.6
0.7
240
15.00
1.00
2520
12
4
144
53
UPS ESTIMATED RUNTIME WITH INTERNAL BATTERIES AND 2
MATCHING
BATTERY CABINETS @ .70pf
Rating
PF
Output
Voltage
Rated I
Rated
Load %
Output
Watts
# Batt
# Strings Nominal
Runtime
3.6
0.7
240
15.00
0.10
252
12
7
144
300
3.6
0.7
240
15.00
0.20
504
12
7
144
300
3.6
0.7
240
15.00
0.30
756
12
7
144
180
3.6
0.7
240
15.00
0.40
1008
12
7
144
165
3.6
0.7
240
15.00
0.50
1260
12
7
144
150
3.6
0.7
240
15.00
0.60
1512
12
7
144
120
3.6
0.7
240
15.00
0.70
1764
12
7
144
112
3.6
0.7
240
15.00
0.80
2016
12
7
144
105
3.6
0.7
240
15.00
0.90
2268
12
7
144
98
3.6
0.7
240
15.00
1.00
2520
12
7
144
86
Summary of Contents for 1600XP SERIES
Page 2: ...b 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 6: ...f 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 10: ...iv 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 74: ...64 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 112: ...B 32 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 115: ...C3 1600XP XPi Series Installation and Operation Manual 60616 012 8 10 kVA Dimensions ...
Page 132: ...E2 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Page 139: ......