Fig. 2.3-3 example of wall side mounting installation for Inlet water level measurement
(2) Installation for storage Tank
Please avoid installing MRF-10 at the very center of tank, because the reflection of
side beam will affect stable measurement.
Besides, please set the lengthwise direction of MRF-10 install to be parallel against
the nearest tank wall. In such case, required free space to the nearest tank wall will
be more than “measuring range x 0.2”.
Fig. 2.3-4 example of tank installation
Note
Any obstructions, which set as parallel to fluid surface in, the radiated beam area
may contain big disturbance noise.
In such case, reflection plate will be one of the solutions to reduce its reflection.
Tank Wall
H
Side of channel
mounting
Any obstructions must not be on this wall.
W
at
er
C
hannel
Flow Direction
Required space = H x 0.5
2-4