[5-3] Search Delay
Parameter
Default Value
Description
1-120
120
Time delay after loss of echo until restart in
accordance with [sec] setting.
[5-4] Alarm Delay
Parameter
Default Value
Description
1-120
120
Time delay after loss of echo until alarm sounds in
accordance with [sec] setting.
[5-5] Bottom Window
Parameter
Default Value
Description
0-0.5
0
Parameter range in metric [m] units
If measurement unit is [ft], display will be converted to show ‘feet’ units.
Valid only when [5-7] is set at “0".
[5-6] First Echo Flag
Parameter
Description
Max Echo
Max strength echo defined as surface echo
First Echo
First echo defined as surface echo
[5-7] Bottom Visible
Parameter
Description
Bottom Visible
When tank bottom echo is larger than
surface echo (such as with oil fluids).
Effective against echo misdetection.
Bottom Invisible
When tank bottom echo is smaller than
surface echo (such as with water, setting
“
Bottom Invisible
”, invalidates this function.
Measurement Range (R)
Peak detectable range
Bottom window
Surface echo
Bottom echo
Distance
Detected as Surface echo
at First Echo setting
Detected as Surface echo
at Max Echo setting
S
ignal
A
mpl
itude
4- 20