[2--] ANALOG Settings
[2-1] Analog output parameter
Parameter
Description
Level
Level value
converted
to 4-20 mA
Ullage
Ullage value
converted
to 4-20 mA
Volume
Volume value
converted
to 4-20 mA
Amplitude
Signal strength amplitude value converted to 4-20 mA
[2-2] Minimum output (4 mA)
Parameter
Output
Default
Value
Description
-3.000-13.000
Level
0.000
Parameter range in metric [m] units
-3.000-13.000
Ullage
0.000
Parameter range in metric [m] units
0.000-100.000
Volume
0.000
[%]
0.000-100.000
Amplitude
0.000
[dB]
When [ft] units are selected for “Level” or “Ullage” display, parameter range is
calculated in ‘feet’.
[2-3] Maximum output (20 mA)
Parameter
Output
Default
Value
Description
-3.000-13.000
Level
10.000
Parameter range in metric [m] units
-3.000-13.000
Ullage
10.000
Parameter range in metric [m] units
0.000-100.000
Volume
100.00
[%]
0.000-100.000
Amplitude
100.00
[dB]
When [ft] units are selected for “Level” or “Ullage” display, parameter range is
calculated in ‘feet’.
[2-4] Alarm selection
Parameter
Value
Description
0
High output
22 mA alarm output
1
Low output
3.9 mA alarm output
2
Hold output
Hold last value
[2-5] Fixed current output setting
Parameter
Value
Description
0
Measuring Value [mA]
3.900-22.000
Fixed current
Any current value selectable
4- 16