Wiring & Connections
Associated Documentation
2-2
DensityPRO with
F
OUNDATION
™ fieldbus
Application Guide
Thermo Fisher Scientific
Note
Refer to
F
OUNDATION
fieldbus
specification for cable sizes and
maximum cable length.
▲
Cable length = trunk all spur lengths
Maximum length = 1900 meters with “type A” cable
Table 2–2.
Spur lengths
Device
Spur Length (meters)
25-32
1
19-24 30
15-18 60
13-14 90
1-12 120
The following table lists the possible jumper settings for the fieldbus board.
Table 2–3.
Jumper settings for fieldbus board
Jumper
Default Setting
Description
SIM
Off
For testing only. Puts interface in a simulation mode.
HW
Off
Hardware write lock. Not supported. (Software write
lock supported. Access WRITE_LOCK parameter
through RESOURCE > Process or Options tab.)