For 30K and 36K units
Check the resistance between every two ports of U, V, W of IPM and P, N first. If any result of them
is 0 or close to 0, the IPM is defective and has to be replaced.
Otherwise, please follow the procedure below:
Refer to Section 9.3.5.
Please refer to the section 9.3.4.
Replace motor if it fails.