9.2.5 E4/E5/F1/F2/F3: Temperature Sensor Open or Short Circuit Error
Condition: Sampling voltage is lower than 0.06V or higher than 4.94V.
Possible Causes:
- Wiring mistake
- Sensor faulty
Check the connection
between temperature
sensor and PCB.
Correct the connection
No
Yes
Replace indoor or outdoor
main PCB
Measure the resistance
value of the sensor
Repalce the sensor
No
Yes
Testing the Resistance of the Sensor
Measure resistance of the
sensor. Refer to Section
9.3.2 for testing details.