42
Setup
Code
Setup Name
Setup Range
Display (on remote
/indoor unit panel)
Default
Setting
Remark
F6
unit operation
CH - Heat Pump
CH
CH
HH - Heating Only
HH
F7
temperature
compensation in cooling
-2°C ~ +2°C
-2 ~ 2
-2
F8
refrigerant detection
ON
ON
"EC" will display on
the indoor panel
while the refrigerant
is not enough.
OFF
F9
air filter clean reminder
ON
After 240 hours of
use, "CL" will flash on
the indoor panel for
15 seconds each time
when the unit
restarts.
OFF
OFF
E1
air freshening filter
change reminder
ON
After 2,880 hours of
use, "nF" will flash on
the indoor panel for
15 seconds each time
when the unit
restarts.
OFF
OFF
E2
lowest setting
temperature
17°C ~ 24°C
(62°F ~ 76°F)
17°C - 24°C
(62°F - 76°F)
17
E3
highest setting
temperature
25°C ~ 30°C
(78°F ~ 88°F)
25°C ~ 30°C
(78°F ~ 88°F)
30
E5
operation priority for
multi zone
H - heating
H
H
Not available for the
single zone mini
splits.
C - cooling
C
E6
network address
0 ~ 63
0 ~ 63
N/A
Cannot check, only
show when the
address changed by
special command. No
set-off memory while
address changed.
E7
capacity selection
0 ~ 11
0 ~ 11
N/A
Cannot be changed.
E8
twins selection
0 ~ 2
0, 1, 2
N/A
Cannot be changed.
E9
static pressure selection 0 ~ 4
0 ~ 4
N/A
Cannot be changed.
Summary of Contents for 12H47YIMI
Page 10: ...10 1080 mm 226 mm 335 mm 30H48ZIMI 49 57 1259 mm 11 1 282 mm 14 25 362 mm 36H46ZIMI...
Page 19: ...19 Model Voltage V Capacity BTU Type 12H47ZOMI 230 12 000 HEAT PUMP...
Page 56: ...56 P W N U...
Page 57: ...57 N V N W...
Page 82: ...82 7 Then lift the PCB assembly off the unit NOTE All wires are still connected...