68
9.3.3 IPM Continuity Check
First turn off the power to the unit and wait approximately 20 seconds to allow the
electrolytic capacitors to fully discharge. Next remove the IPM from the PCB. Use a
multimeter to measure the resistance between P & UVWN; UVW & N. See the table below
for proper resistance values.
Position
Resistance
(+) Red
(-) Black
∞
(Several MΩ)
P
N
U
V
W
U
N
V
W
(+) Red
9.3.4 Outdoor AC
Fan Motor Check
To check if the outdoor fan motor is working properly, measure the resistance value of
each winding with a multimeter.
Position
Resistance @ 68°F (20°C)
9H47YOMI
YKT-32-6-202L
12H47YOMI
YKT-32-6-202L
12H47ZOMI
YKT-32-6-3L
18H47ZOMI
YKT-48-6-206
24H46ZOMI
YKT-63-6-200L
Black
–
Red
Main
86
Ω
213
Ω
152
Ω
88.5
Ω
White
–
Black
Aux
64
Ω
156
Ω
142
Ω
138
Ω
Summary of Contents for 12H47YIMI
Page 10: ...10 1080 mm 226 mm 335 mm 30H48ZIMI 49 57 1259 mm 11 1 282 mm 14 25 362 mm 36H46ZIMI...
Page 19: ...19 Model Voltage V Capacity BTU Type 12H47ZOMI 230 12 000 HEAT PUMP...
Page 56: ...56 P W N U...
Page 57: ...57 N V N W...
Page 82: ...82 7 Then lift the PCB assembly off the unit NOTE All wires are still connected...