25
4.
Operate the air conditioner at the cooling mode.
5.
Open the valves (low side) on the charge set and charge the system with liquid refrigerant.
6.
When the electronic scale displays the proper weight (refer to the gauge and the pressure of the
low side), disconnect the charge hose from the 3-
way valve’s service port immediately and turn
off the air conditioner before disconnecting the hose.
7.
Mount the valve stem caps and the service port. Use torque wrench to tighten the service port
cap to a torque of 13.3ft·lb (18N·m). Be sure to check for gas leakage.