9.2.10 P6: Low Pressure Protection Diagnosis and Solution
Condition: When the pressure of system reach a certain value, the pressure protector
will switch off. After the pressure resume to normal, the protection code will extinguish.
Possible Causes:
- Wiring mistake
- Pressure protector faulty
- Outdoor fan assembly faulty
- System problems
- Outdoor PCB faulty
For 36K unit only
Please refer to the section 9.3.4.
Replace motor if it fails.