9.2.4 E3/F5: Fan Speed Out of Control Error
Condition: Indoor fan speed stays too low (300 RPM) for a certain time.
Possible Causes: - Wiring mistake
- Fan assembly faulty
- Fan motor faulty
- PCB faulty
Power off, then restart the
unit 2 minutes later
Shut off the power supply,
Rotate the fan by hand.
The unit operates normally.
Find out the cause and have
it solved
Check the wiring of fan
motor
No
Yes
No
Correct the connections.
No
No
Replace the fan motor
Yes
Yes
Measure the voltage for the
fan motor from the main
PCB
Yes
Replace the main PCB
No