32
8.4 Operation Modes and Logic
8.4.1 Fan Mode
•
Outdoor fan and compressor stop running.
•
Temperature setting is disabled and not shown.
•
Indoor fan can be set to high/med/low/auto.
•
Louver operates in the same way as cooling mode.
•
Auto fan logic
8.4.2 Cooling Mode
8.4.2.1 Compressor Operation Logic
When T1-Ts<
Δ
T - 3.6 °F, the compressor will stop,
When T1
—
Ts >
Δ
T - 1°F
,
the compressor will be activated.
Δ
T is the programmed parameter of temperature compensation.
When Silence feature is activated, the compressor will run with low frequency.
When the current is more than setting value, the current protection function will be activated,
and the compressor will stop.
8.4.2.2
Outdoor Fan Logic
The outdoor unit will be run at different fan speed according to T4.
For different outdoor units, the fan speeds are different.
8.4.2.3 Indoor Fan Logic
When the compressor is on, the indoor fan can be set to high/med/low/auto. And the anti-cold
wind function has the priority.
The indoor fan is controlled as below:
Setting fan
speed
Actual fan speed
H+(H+=H+G)
A
H(=H)
B
C
M+(M+=M+Z)
D
M(M=M)
E
F
L+(L+=L+D)
G
L(L=L)
H
I
T1-Td
℃
(°F)
L
L-(L-=L-D)
H
H-(H-=H-G)
M
M-(M-=M-Z)
a
b
c
d
T1
°F
e
a
b
c
d
T1
°F
e
Summary of Contents for 12H47YIMI
Page 10: ...10 1080 mm 226 mm 335 mm 30H48ZIMI 49 57 1259 mm 11 1 282 mm 14 25 362 mm 36H46ZIMI...
Page 19: ...19 Model Voltage V Capacity BTU Type 12H47ZOMI 230 12 000 HEAT PUMP...
Page 56: ...56 P W N U...
Page 57: ...57 N V N W...
Page 82: ...82 7 Then lift the PCB assembly off the unit NOTE All wires are still connected...