Eclipse 8/ 16/ 32 Series - Engineer Programming Manual
56
POSTPONE
AA
ADDRESS
4003
OPERATION
403
TEXT MENU
6. PARTITIONS – 4. POSTPONE TIME
Automatic arming delay from Manager
Enter a time from 001 to 255 minutes.
The Engineer sets a time for automatic arming delay on time slot from Manager. During of a running
automatic arming procedure on set time slot, (address 4xx9, where “xx” is the area number) entering
of Manager code will call several addition options on the
display. Choosing the “POSTPONE” option
will delay the automatic arming with the set time at this address, as the set time must be greater
than 1 minute.
If at the time of arming, the area is not ready to be armed, the automatic arming procedure will be
delayed until the area is ready to be armed, and will be armed in the next 1 minute.
Default setting: [010]
AREA 1
EXIT
ADDRESS
4010
OPERATION
410 + 01
TEXT MENU
6. PARTITIONS – 5. AREAS – 1. AREA – 01. EXIT TIME
Setting of exit time for Area 1
Exit time is assigned to Entry/Exit type zones associated to Area 1. A 3-digit number between 000
and 255 seconds is entered. For an interval of time, less than 10 seconds, the first two digits must
be 0.
In case of command for arming of two or more areas, with a common Entry/Exit type zone then
every area will be armed only when its own set exit time is over. The common zone will be bypassed
in the already armed areas until and the last one area is armed. For example, the Zone 01 is
associated to all areas in the system, and when the seven of them are armed the Zone 01 will be
bypassed until and the last area 8 is armed too.
Default setting: 045 seconds
AREA 1
ENTRY
ADDRESS
4011
OPERATION
411 + 01
TEXT MENU
6. PARTITIONS – 5. AREAS – 1. AREA – 02. ENTRY TIME
Setting of entry time for Area 1
Entry time is assigned to Entry/Exit type zones associated to Area 1. A 3-digit number between 000
and 255 seconds is entered. For an interval of time, less than 10 seconds, the first two digits must
be 0.
When during running of entry time after opening of Entry/ Exit type zone associated to more than
one area in the system, a valid user code associated to at least one of those areas is entered, then
the common area will be disarmed and the other areas will stay armed. The common Entry/ Exit
type zone will be bypassed in the left armed areas.
When one of the armed areas is in alarm mode and a valid code associated to other area is entered
(but both areas have a common zone) the siren stops (if it is associated to the same area) and the
alarm cycle continues as set. Then an alarm message is sent to the monitoring station, and the
event is recorded in the LOG file. An alarm event is generated when the entry time is over
regardless that the violated zone is restored or not.
Default setting: 015 seconds