Eclipse 8/ 16/ 32 Series - Engineer Programming Manual
48
3
DELAY
sec / min*
This option concerns the set value at ADDRESS 3019
– time delay for
activation of PGM 01:
DELAY seconds
(
)
– the set time delay at address 3019 is measured
in seconds.
DELAY minutes
(3)
– the set time delay at address 3019 is measured
in minutes.
4
PULSED
FIRE
ENABLE
This option is available when the PGM 01 is set as a siren output.
When the option is enabled, the output operates in a specific working
mode:
On
Off
1
Sec
1
1
3
1
1
1
3
PULSED FIRE DISABLE
(
)
– The option is not active
PULSED FIRE ENABLE
(4)
– The option is active
5
Deact.
Timer*
This option concerns the set value at ADDRESS 3017
– deactivation
timer for PGM 01:
Deact. Timer seconds
(
)
– the set time at address 3017 is measured
in seconds.
Deact. Timer minutes
(5)
– the set time at address 3017 is measured
in minutes.
For LED
keyboards: The option status “
”
is performed with non-lighting zone number.
* NOTE: The option is not applicable when the PGM is programmed as Siren output.
Default settings: 1. GENERAL OUTPUT, 2. POLARITY NORMAL (+12V), 3. DELAY sec,
4.PULSED FIRE DISABLED, 5. DEACT. TIMER sec.
By default
PGM 05 is programmed as a siren output
– at address 3051 is set “1”. If after the initial power-up of
the control panel, no siren is connected to PGM 05 output, the system will display a trouble message
“8.
SIREN FAULT
”. In case the PGM 05 will be used as a general output, the setting at address 3051 must be
programmed as “
”. You can leave the set by default option, but to void the displayed trouble message in that case
terminate the PGM 05 output with 1kOm resistance
– you can find one in the supplied spare parts kit.
Example with using 4-digit address menus
3051>PGM5
OPT
[*****___]
3051>PGM5
OPT
[1****___]
Output with general purpose
Siren output
Example with using text menus
Select in sequence: 5. OUTPUTS
– 2. PGMs – 05. PGM – 2. P5 OPTIONS. The screen displays:
Output with general purpose
Siren output