19
DOOR Series -
English
TABLE 6
Programming from
control unit
Programming from
selector switch
Functions related to the S2 MINIDIP
or to LED
with programming from the
selector switch
It automatically increases the pause time if the door cannot be closed due to high traffic.
The pause time is kept at a constant value with the dip-switch in the OFF position.
It activates work program selection via the DOORSELF mechanical selector switch (see
paragraph 17).
N.B. keep the DIP switch in the OFF position if you use the DOORPROG digital selector
switch or if a simple switch is used on the AUX1 input to manage the day function (switch
on) or night lock function (switch off).
It activates the STEP-BY-STEP function (an impulse opens, an impulse closes, etc.). With
this function, the active inputs are: emergency
and start
.
With dip on OFF position, automatic door closing is always enabled.
Set at ON if the automation is
SINGLE-LEAF
opening to the
RIGHT. N.B. With LEFT hand
DOUBLE-LEAF or SINGLE-LEAF, keep the DIP in the OFF position.
For “BLOW / BLOW-X” telescopic doors, set to ON if the device is for a single wing
opening towards.
Together with
switch 8
it selects the
DOORFOTO1
photocell card (if installed) and the op-
erating mode of photocell
FR3/FT3.
Refer to
TABLES 1 and 2
in
chapter 12.3
for instruc
-
tions on how to use this switch.
WARNING: keep the dip-switch OFF if photocell DOORFOTO1 is not installed.
N.B. It activates the initial setting cycle. Read carefully the chapter regarding this
operation.
ON = FUNCTION FOR FIRE DOORS (see section 20)
WARNING: Activate the function before making the INITIAL SETUP described in SECTION
15.
OFF =standard function for INTERLOCK input activated as door stop.
Together with
switch 5
it selects the
DOORFOTO1
photocell card (if installed) and the op-
erating mode of photocell
FR3/FT3
. Refer to
TABLES 1 and 2
in
chapter 12.3
for instruc
-
tions on how to use this switch.
WARNING: keep the dip-switch OFF if photocell DOORFOTO1 is not installed.
The door closes immediately if the radars and photocells are not activated (the other inputs
work normally).
With the dip-switch OFF, the door carries out a complete opening, pause and closing cycle
on each radar detection.
It activates the programming of the
POTENTIOMETER DIPS
from the
DOORPROG.
selec
-
tor switch. After setting this DIP at ON, execute a complete open and close cycle in order
to activate this function (the dips and potentiometers on the control unit have no effect).
N.B. if this DIP is left at OFF, it will not be possible to switch the position of DIPS 1
to 10 of S1 and S2 and of potentiometers TM1 to TM7 from the DOORPROG selector
switch.
11
Operation of LOCK2 output in the INTERLOCK function (see paragraph 16):
OFF: it is activated 0.5” before the opening of the door;
ON: it is activated at the same time as the door opens.
12
N.B. function not enabled, keep the DIP in the OFF position.