15_ ADJUSTING THE AUTOMATISM
After having fixed the door wings to the rails, make sure that they slide smoothly., then make all the electrical connections described in
section 11 and comply with the INITIAL SETUP PROCEDURE. This operation is OBLIGATORY, since it allows the control unit to acquire
all the data without which it would not be able to operate (door wing weight, limit switches, inertia, etc.).
STRICTLY COMPLY WITH THE FOLLOWING CHAPTER WHEN THIS OPERATION IS CARRIED OUT.
15.1_ INITIALIZATION PROCEDURE (INITIAL SETTING)
WARNING: the initialization procedure is the phase during which the automation learns and samples all the factors which
will affect its subsequent operation. Execute the procedure only after performing the operations described in the previous
chapters.
IMPORTANT: be careful to remove all obstacles from the doorway and from the radar detection range during the initialisation
procedure, otherwise the procedure will fail and will have to be repeated. The door must not be helped manually and the
settings of the potentiometers must not be modified. The initialisation procedure will have to be repeated if any of the following
parameters are modified: leaf travel, leaf weight, opening direction, type of motor (DOORX or DOOR).
1_
Make sure that the mains power source is OFF, then temporarily disconnect the battery-powered opening device DOORBATT if
installed.
2_
Set all the minidips (S1 e S2) at OFF.
3_
If you are using a DOORX, set DIP7 of S1 at ON, otherwise leave it in the OFF position.
4_
If you use the DOORPROG SELECTOR switch, leave DIP SWITCH 2 of S2 in the OFF setting; if you use the DOORSELF
mechanical selector switch, set it to ON. Set the knob of the DOORSELF mechanical selector to traffic in both directions or to
NIGHT LOCK.
5_
If the automation is a RIGHT-HAND OPENING LEAF, set DIP4 of S2 at ON, otherwise leave it in the OFF position.
6_
If the door is a fire dor and a smoke sensor is connected to the INTERLOCK input, set DIP 7 of S2 ON, otherwise leave it OFF.
7_
If you have installed the DOOR PHOTO1 PHOTOCELL CARD, set DIP5 of S2 at ON, otherwise leave it in the OFF position.
8_
Check to make sure that potentiometers TM3 (pushing power on opening) and TM4 (pushing power on closing) are set between
halfway and the maximum value.
9_
Power the system and wait for the initial beep to sound.
10_ Disconnect the power supply and wait for 3 seconds.
11_ Set DIP6 of S2 at ON.
12_ Power the system and wait for the double initial beep to sound.
13_ Press the START control (or the PS1 button on the control unit).
The door will begin a Closing / Opening / Closing cycle at slow speed which it must necessarily complete if the initial setup is to be
successful. At the end of a manoeuvre, a long BEEP will indicate that the procedure has terminated correctly.
14_ By leaving DIP 6 of S2 ON, the door thrust can be checked by means of the buzzer. Its effective intensity can be ascertained by
obstructing its movement. This should cause the door to stop immediately and then reverse its direction.
Poteniometers TM3 and TM4 can be used to regulate the door’s pushing power in the opening and closing phases, respectively,
and to calibrate the activation threshold with precision.
A very brief signal from the buzzer during start-up indicates that the pushing force has been well calibrated, while intermittent
signals as the door moves indicate that the pushing force is insufficient.
Set DIP 6 of S2 to the OFF position to inhibit the buzzer signal that indicates limited power.
Once the initialisation procedure has been performed, you can select the work program best suited to the application among the ones
available, you can modify the door speed, change the times and distances etc. There are two ways of performing these operations:
a) directly from the control unit;
b) through remote programming from the selector switch;
15.2_ ADJUSTING THE AUTOMATISM FROM THE CONTROL UNIT
Operate
MINIDIPS S1
and
S2
to select the programs listed in
TABLES 5 and 6
.
Operate potentiometers
TM1
to
TM7
to modify the parameters listed in
TABLE 7
.
Any regulations that cannot be made from the control unit due to the absence of additional dip switches or potentiometers can be made
only using the DOORPROG digital selector switch.
15.3_ ADJUSTING THE AUTOMATISM THROUGH REMOTE PROGRAMMING FROM THE SELECTOR SWITCH
To enable remote programming, first of all
DlP10 of S2 must be set at ON
.
To access the programming mode follow these steps:
a)
Set the selector switch’s
locking key
in the
locked functions
position
.
b)
Press and hold down the selector switch’s
SET
button
.
c)
Return the
locking key
to the
free functions
position
.
d)
Release the
SET
button
.
e)
The inputs LED’s will light up sequentially
from left to right
to signal the loading of the data
(UPLOAD)
.