DOOR Series -
English
TABLE 5
Programming from
control unit
Programming from
selector switch
Functions related to the S1 MINIDIP
or to LED
with programming from the
selector switch
W
O
R
K
P
R
O
G
R
A
M
S
OFF OFF OFF
In the day functions, the electric block is released (powered) and all the control inputs are
enabled. In NIGHT LOCKING mode the door cannot be opened.
ON ON OFF
In the day functions, the electric block is released (powered) and all the control inputs
are enabled. With the DOORPROG selector switch set to the NIGHT LOCKING mode,
the door opens 10” and stays open before re-closing. It can be opened again only via the
emergency input
.
OFF ON OFF
In the day functions, the electric block is released (powered) and all the control inputs are
enabled. With the DOORPROG selector switch set to the NIGHT LOCKING mode, the door
can be opened using the emergency input
.
OFF OFF ON
Bank function. The door locks the leaves at each closing through the electric block in the
day functions; in the night locking mode the door cannot be opened.
BATTERY OPENING MODE. In the event of a power failure, if the program selector switch
is set to one of the day functions, the door opens and stays open until the power supply has
been restored.
WARNING: if the dip switch is set to OFF, in the event of a power failure the door can be
opened using the emergency input
.
BATTERY MONITORING. With the battery exhausted or damaged, the door will open and
stay open in the day functions.
WARNING: if the dip switch is set to OFF and the battery is exhausted or damaged, the
control unit will sound a beep for 1” before performing any opening manoeuvres.
This beep is sounded for the first 10 manoeuvres starting from detection of the event in the
day functions.
In the event of a power failure, in the battery operating mode the door can be opened via all
the control inputs. To enable the radars to operate in battery mode, the power supply must
be drawn from terminals 1(+) and 3 (-) of the M1 terminal board.
WARNING: if the dip switch is set to OFF and there is a power failure, the door can be
opened only using the EMERGENCY input.
Before performing the initial setting of the control unit, set the parameters for motor man-
agement: ON=DOORX; OFF=DOOR.
After completing the initial setting procedure, when the door is in work mode, select the
operating mode for the LOCK2 output:
OFF = PHARMACY function;
ON = AIR BLADE or OPEN DOOR INDICATOR LIGHT man-
agement (see paragraph 18).
It activates the cyclic opening function (open and close cycle repeated until the DIP is
switched back to OFF).
N.B.: Use this function only for internal testing purposes.
If the door cannot be closed in winter mode
due to high traffic, after approx. 1’ it switch-
es to fully open. It will return to winter mode after a complete closing manoeuvre.
With the dip-switch OFF, the door always stops at the winter opening point.
WARNING: Function disabled. Keep the DIP in ther OFF position.
11
Keep in the PFF position!!
This dip is used for resetting the default values of the TECHNICAL MENU (see section
21).
12
Activates the interlock function (see paragraph 16).
It makes the interlock input operational; if this input is engaged, the door can be opened
only via the EMERGENCY button.