3 Connection and Basic Functions
TAC Xenta, TAC Xenta OP
24 (46)
TAC AB, July 2007
04-00065-01-en
•
ON
OP permanently electrically connected to the network; installed
with a binding tool.
Confirm your choice by pressing
.
3.7
Remove the OP
If the OP is to be removed from the network, it should be restored to the
original factory setting to avoid problems, if used in another network.
Depending on which binding tool has been used, the removal is made
according to one of the methods shown below.
3.7.1
Tool: MetraVision
1
Select OP Service menu
⏐
10.
OP mode
and set
Bindable
to
TAC
or, in OP version < 3.11,
OFF
.
2
Disconnect the OP electrically from the network.
3
“
Remove
” the OP node from the data base.
Factory setting
If the OP has been labelled ”Unconfig”, which may happen if step 3
above was executed before step 2, or for any other reason; the OP may
be restored to the factory setting in one of two ways:
•
Reconnect the OP to the network, reinstall it and perform the steps
above in the correct order, or
•
Use the Nodutil program and do the following.
Select OP Service menu
⏐
10.
OP mode
and set
Bindable
to
TAC
or,
in OP version < 3.11,
OFF
.
1
Start Nodutil.
2
Press the Service pin of the OP.
3
Type “G”.
4
Type “1”, press Enter.
5
Type “M”.
6
Type “S”.
7
Type “C”.