TAC Xenta, TAC Xenta OP
3 Connection and Basic Functions
TAC AB, July 2007
25 (46)
04-00065-01-en
3.7.2
Tool: LonMaker
1
Check in the OP Service menu
⏐
10.
OP mode
that
Bindable
is
set to
TAC
or, in OP version < 3.11,
OFF
.
2
Start the LonMaker Browser.
3
Right-click, and then click
Properties
.
4
Disconnect the OP electrically from the network.
5
Remove the OP from the data base of LonMaker.
Factory setting
If the OP has been de-installed in an incorrect way, it may be restored
to the factory setting in one of two ways:
•
Reconnect the OP to the network, reinstall it and perform the steps
above in the correct order, or
•
Use the Nodutil program and perform the following.
1
Select OP Service menu
⏐
10.
OP mode
and set
Bindable
to
TAC
or, in OP version < 3.11,
OFF
.
2
Start Nodutil.
3
Press the Service pin of the OP.
4
Type “G”.
5
Type “1”, and then press Enter.
6
Type “M”.
7
Type “S”.
8
Type “C”.
9
Type “U”.
10
Type “2”, and then press Enter.
11
Type “00”, and then press Enter.
Note
•
Restore SNVT_config_src from cfg_external (1) to cfg_local (0).
SNVT_config_src is called var_2 in the Browser.