TAC Xenta, TAC Xenta OP
3 Connection and Basic Functions
TAC AB, July 2007
23 (46)
04-00065-01-en
To turn OFF the Xenta 100 mode
3.6.2
Bindable
“Bindable” is a LonWorks term, describing how the OP is connected
and addressed in the network. This, in turn, affects the mobility of the
OP.
Use
or
to select Bindable mode from the following:
•
TAC OP movable.
Two available addresses following each TAC Xenta Base unit.
•
INST
OP permanently electrically connected to the network; installed
with a binding tool.
•
MAN
OP movable, the domain ID of the network has to be programmed
via OP Service menu – 4.LON address (communication is here lim-
ited to Base units on the same channel).
For OP version 3.11 and earlier the following modes can be chosen:
•
OFF
OP movable. Two available addresses following each TAC Xenta
Base unit.
Press enter to
access Xenta
100(wait)
Connecting to
Xenta Base unit
1. Disconnect and then) connect the OP;
wait for a couple of seconds for the Base
unit message to appear.
2. Press both keys
and
for
about three seconds simultaneously.
OP Service menu
1. Exit service
mode
2. Keyboard test
3. Display test
10 OP mode
3. Select 10. OP mode menu.
Change OP mode
Xenta 100 : OFF
Bindable : TAC
4. Press
or
to set the Xenta
100 mode ON and press
.
1. Exit service
mode
5. Select the 1. Exit service mode menu
and press
.
+
–
+
–