116
Fan Speed Demand (for SRC-701)
Unsigned 16
0..1000
0..100.0 %
117
Thermic1 Demand
Unsigned 16
0..1000
0..100.0 %
118
Thermic2 Demand
Unsigned 16
0..1000
0..100.0 %
200
Firmware Versions
Unsigned 16
N/A
N/A
FUNCTION CODE 03 - READ HOLDING REGISTERS (For Modicon Addressing Add 40,000)
FUNCTION CODE 06 - WRITE SINGLE HOLDING REGISTER
FUNCTION CODE 16 - WRITE MULTIPLE HOLDING REGISTERS
100
Nominal Setpoint
Unsigned 16
0...950
0.0...95.0°C/°F
(Default 20°C)
101
Heating Comfort Deadzone
Unsigned 16
0...250
0.0...25.0°C/°F
(Default 0.5°C)
102
Cooling Comfort Deadzone
Unsigned 16
0...250
0.0...25.0°C/°F
(Default 0.5°C)
103
ECO Heating Deadzone
Unsigned 16
0...250
0.0...25.0°C/°F
(Default 4.0°C)
104
ECO Cooling Deadzone
Unsigned 16
0...250
0.0...25.0°C/°F
(Default 4.0°C)
105
Frost Setpoint
Unsigned 16
0...950
0.0...95.0°C/°F
(Default 8°C)
106
Setpoint Adjust Minimum
Signed 16
-200..0
-20.0..0.0 °C/°F (Default -3.0)
107
Setpoint Adjust Maximum
Signed 16
0..200
0.0..20.0 °C/°F (Default 3.0)
108
Temperature Control Proportional Band
Unsigned 16
10...500
1.0...50.0°C/°F
(Default 4°C)
109
Temperature Control Integral Action Time
Unsigned 16
0..1200
0..1200 seconds (600s default)
110
Number of Heating Stages
Unsigned 16
0..2
0 = None
1 = 1-Stage (Default)
2 = 2-Stages
111
Heating Stage 1 Direction
Unsigned 16
0..1
0 = Reverse (Default)
1 = Direct
112
Heating Stage 2 Direction
Unsigned 16
0..1
0 = Reverse (Default)
1 = Direct
113
Number of Cooling Stages
Unsigned 16
0..2
0 = None
1 = 1-Stage (Default)
2 = 2-Stages
114
Cooling Stage 1 Direction
Unsigned 16
0..1
0 = Reverse
1 = Direct (Default)
115
Cooling Stage 2 Direction
Unsigned 16
0..1
0 = Reverse
1 = Direct (Default)
116
High Limit Setpoint
Unsigned 16
0...950
0..95°C/°F (Default 35.0°C)
117
Low Limit Setpoint
Unsigned 16
0...950
0..95°C/°F (Default 16.0°C)
118
Limit Ratio
Unsigned 16
0..50
0.0..5.0 (0.0=Disabled, Default)
119
CO2 Control Setpoint
Unsigned 16
0..5,000
0..5000ppm (Default 1,000 ppm)
120
CO2 Proportional Band
Unsigned 16
10..5,000
10..5000 ppm (Default = 300 ppm)
121
CO2 Control Integral Action
Unsigned 16
0..10,000
0..10,000 seconds (Default 0)
122
CO2 Output Direction
Unsigned 16
0..1
0 = Reverse Acting
1 = Direct Acting (Default)
123
Humidity Control Setpoint
Unsigned 16
0..1000
0.0...100.0 %rH (Default 50%)
124
Humidity Proportional Band
Unsigned 16
10..1000
1.0...100.0 %rH (Default 20.0%)
125
Humidity Control Integral Action
Unsigned 16
0..10,000
0..10,000 seconds (Default 0)
126
Humidification Output Direction
Unsigned 16
0..1
0 = Reverse Acting
1 = Direct Acting (Default)
127
De-Humidification Output Direction
Unsigned 16
0..1
0 = Reverse Acting
1 = Direct Acting (Default)
128
Fan Speed Display
Unsigned 16
0..5
0 = No Display (Default)
1 = Display Only (no user adj.)
2 = 0 - 1 (0%, 100%)
3 = 0 - 1 - 2 (0%, 50%, 100%)
4 = 0 - 1 - 2 - 3 (0%, 33%,
66%,100%)
5 = 0 - 1 - 2 - 3 - 4 - 5 - 6
Register
Parameter Description
Data Type
Raw Data
Range