Humidity Cal.
Humidity Calibration (RH Models)
-10.0..+10.0 % rH
Y1
Analogue Output Y1 Mode
Default: Modulating Fan
NOTE: With SRC-701, 703 and 704 do not change
this setting - leave to default.
0 = Network Value
1 = Heating Stage 1
2 = Heating Stage 2
3 = Cooling Stage 1
4 = Cooling Stage 2
5 = Modulating Fan (EC)
6 = CO2 Control
7 = Maximum VAV
8 = Maximum Fan
9 = Humidification
10 = De-humidification
11 = Amber / Red
12 = Red
13 = Heating Stage1 Sta
14 = Cooling Stage1 Stat
15 = Fan Stat
16 = Aux Loop
17 = 6-Port (Valve)
18 = 6-Port Reverse (Valve)
Y2
Analogue Output Y2 Mode
Default: Heating Stage 1
SRC-703 Default: Heating Stat1
NOTE: Not available with SRC-702/704H.
Y3
Analogue Output Y3 Mode
Default: Cooling Stage.
NOTE: Not available with SRC-702/704H.
Y1 Min.
Analogue Output Y1 Minimum Value
0..100%(0% = default)
Y1 Max.
Analogue Output Y1 Minimum Value
0..100% (100% = default)
Y2 Min.
Analogue Output Y2 Minimum Value
0..100%(0% = default)
Y2 Max.
Analogue Output Y2 Minimum Value
0..100% (100% = default)
Y3 Min.
Analogue Output Y3 Minimum Value
0..100%(0% = default)
Y3 Max.
Analogue Output Y3 Minimum Value
0..100% (100% = default)
Anti-JAM
Valve Exercise
0..14 Days (default 0 = disabled)
PWM Period
PWM Period (SRC-702/SRC-704H)
0..120 Seconds (default 30)
INPUTS & OUTPUTS
Parameter Name
Description
Range
FAN, BOOST, TIMES
Parameter Name
Description
Range
Fan Speed Display
Selecting the Fan Speed (User Adjustment) for the
Display
Note: Modes 2,3,4 set the number of steps the user
can manually adjust the fan speed.
0 = None (Default)
1 = No Input (no user adj.)
2 = 0 - 1 (0%, 100%)
3 = 0 - 1 - 2 (0%, 50%, 100%)
4 = 0 - 1 - 2 - 3 (0%, 33%,
66%,100%)
5 = 0 - 1 - 2 - 3 - 4 - 5 - 6
Fan Speed Source
Fan Speed Control Source
(The fan speed follows theselected control loop
output. The minimi Fan Level parameter applies in
operation)
0 = Heating 1 and Cooling 1 Stage
(Default)
1 = Heating Stage1
2 = Cooling Stage 1
3 = Heating and Cooling Stage 2
4 = Heating Stage 2
5 = Cooling Stage 2
6 = CO2
7 = Humidification
8 = De-Humidification
9 = Maximum VAV (Cooling/CO2)
10 = Maximum Temp/Hum
11 = Aux. Loop
Min Fan Level
Fan Speed Minimum Active Level
0...100% (Default 0%)
Fan Off Delay
Fan Switch Off Delay when Fan Speed Source
Demand < Min Fan Level.
Note: Only active if Min Fan Level is set.
0...28,800 seconds (Default = 0)
0 = Infinite
Boost Time
Boost Mode Running Time
0 = Permanent
1..480 minutes (Default 0)
Boost Target
Boost Button Target Operation
0 = Nominal SP (Temperature)
1 = CO2 SP
2 = Humidity SP
3 = Dehum SP
4 = Fan Demand
5 = Aux. Temp SP
Boost Setpoint Value
Boost Setpoint Value, The target value that the
boost button affects (whole integers).
0...5000 (default 25)