SRC-P-700 Series User 
Interface

The figures below illustrate some of the SRC-P-700 controller user displays. The multi-colour LCD 
screen is touch sensitive, easy to adjust and illustrates clearly the plant status information.

HEATING DEMAND

Room

20

.1

°C

STATUS INFORMATION 
BANNER

INTENSITY OF THE RED ON 
THE ENERGY RING 
CHANGES DEPENDING ON 
DIFFERENCE BETWEEN 
EFFECTIVE TARGET AND 
ROOM TEMPERATURES, AT 
2°C/3.6°F FULL RED

COOLING DEMAND

Target

21

.5

°C

PRESS DIM BUTTON TO 
SWITCH BACKLIGHT OFF

TARGET SETPOINT 
ADJUSTMENT BUTTONS

Outside

10

.5

°C

Humidity

45

%

Humidity

45

%

CO2

700

ppm

TRANSITIONS BETWEEN
ROOM, HUMIDITY, CO2, 
OUTSIDE (NETWORK)

FAN STATUS AND 
MANUAL CONTROL 
(FAN ROTATES 
WHEN RUNNING)

Target

21

.5

°C

A

A

OK

CO2 AMBER 
ALARM

CO2

700

ppm

CO2 ALARM DISPLAYS

CO2 RED ALARM

CO2

950

ppm

CO2

1300

ppm

SMALL ACTION 
CIRCLE

INDICATES 
CURRENT MODE - 
BUTTON FOR 
MODE SCREEN 
ACCESS

OFF (AWAY) MODE -
BUTTON TO MODE 
SELECTIO SCREEN

Wed 12:43

Wed 12:43

WHEN ENTERING THE MODE 
SCREEN THE CURRENT MODE 
STATUS IS DISPLAYED.

BY SELECTING THE NEW MODE 
THE DEVICE AUTOMATICALLY 
RETURNS TO THE HOME 
SCREEN (OR AFTER TIMEOUT).

MODE SCREEN

The colour of the ’Energy Ring’ indicates the heating/cooling demand. The ’Energy Ring’ is white at 
’deadzone’. The density of red/blue on the ’Energy Ring’ modulates based on how far from the 
Effective Heating/Cooling Setpoint the temperature is. When the difference is 2°C/3.6°F the ’Energy 
Ring’ is at full density

calcSP

HDz

MEASURED 
TEMPERATURE

+

-

CDz

Deadzone

ENERGY RING COLOURS

HDz - 2°/ 3.6°F

CDz + 2° / 3.6°F

.

Touchscreen

The SRC controller home screen has a number touch sensitive areas that allow the device settings to 
be changed.

UP and DOWN arrows; to alter the current control target setpoint temperature

SCREEN DIM ICON; dims the screen backlight/ switches backlight off

SMALL ACTION CIRCLE (that contains current room and/or floor temperature, CO2, humidity 
etc); allows access to FURTHER SETTINGS AND INFORMATION screen; password protected

FAN SPEED ICON; when FAN display is enabled, the fan ICON can be used to control the fan 
speed

COMFORT/ECO/OFF/BOOST ICON; used to select between COMFORT/ECO/OFF/BOOST 
modes. When selected, the MODE SELECTION screen is displayed and can be used to select 
the mode.

Programming Times and 
Targets

The SRC-700 controllers have up to five programmable time switching times that can be configured to 
switch between COMFORT / ECO / OFF / BOOST modes. The times and targets can be set for 
individual weekdays or the thermostat can be switched 5+2 mode where the targets are set for 
WEEKDAYS or WEEKENDS.

The SCHEDULE OVERVIEW screen shows the current switching targets. By selecting the day it is 
possible to adjust the switching times and targets of the device.

NOTE: Switching from the 7 DAYS mode to 5+2 DAYS mode will set all weekday/weekend to the 
group settings. When returning back to 7 DAYS mode the setting are required to be re-entered for 
each day. 

Summary of Contents for SRC-P-700 Series

Page 1: ...ic Summer Winter Time Change Over Product sheet CT2 161 Type SRC P 700 Product Selection Table 1 2 3 4 5 6 1 Device type Touchscreen Room Controller 2RI 1DI 3AO htg clg fan Schedule SRC P 700 Touchscr...

Page 2: ...maximum 63 devices MAC Addressing 0 127 via Touchscreen Device ID Default 651000 MAC Address Adjustable Communication 9k6 19k2 38k4 57k6 76k8 Baud Parity None Even Odd 1 or 2 Stop Bits adjustable thr...

Page 3: ...ommon RI1 Remote NTC10 Temperature Sensor Input 1 0 10V with AI option RI2 Remote NTC10 Temperature Sensor Input 2 0 10V with AI option Din Volt Free Digital Input Contact dry contact 485A Modbus BACn...

Page 4: ...nput 1 0 10V with AI option RI2 Remote NTC10 Temperature Sensor Input 2 0 10V with AI option Din Volt Free Digital Input Contact dry contact 485A Modbus BACnet MS TP RS485 A Connection 485B Modbus BAC...

Page 5: ...n Speed 1 On Off Valve RCOM Relay Common RLY2 230V 7A Relay Fan Speed 2 RLY3 230V 7A Relay Fan Speed 3 TR2 24Vac 1A Triac switched to 0V default Cooling PWM 24V 24Vac dc Supply G0 0V Common TR1 24Vac...

Page 6: ...Ring modulates based on how far from the Effective Heating Cooling Setpoint the temperature is When the difference is 2 C 3 6 F the Energy Ring is at full density calcSP HDz MEASURED TEMPERATURE CDz...

Page 7: ...in the stand by level switches the backlight OFF The screen backlight is automatically activated when it is touched Further Settings and Information The FURTHER SETTINGS screen shows additional user...

Page 8: ...re to fluctuate around the setpoint without heating or cooling valves starting to open The SRC has a built in lock that prevents cooling and heating demands to be on simultaneously The deadzone has an...

Page 9: ...target setpoint on the display is not changed during the limitation The limit icon indicates active limitation To see the effective limited setpoint enter Controller Status and Information display Not...

Page 10: ...C 6 0 0 6 0 1 6 0 2 0 1 0 V d c S R C 6 0 2 P W M Note If the 7 Day Schedule has been activated the device starts to use the operating mode set at the next switching point e g if the next switching p...

Page 11: ...chedule point regardless of the Boost Time or Current Measurement Please note that at the next switching time the target COMFORT ECO OFF BOOST must be different from the target in the current period i...

Page 12: ...O MATIC CONTROL 6 SPEED MANUAL FAN CONTROL M 17 33 0 50 67 83 100 A Auto SPEED SET BY CONTROLLER 100 0 50 100 0 33 67 0 100 M M M M M M M M M M M M A Auto SPEED SET BY CONTROLLER A Auto SPEED SET BY C...

Page 13: ...e actuators 100 CONTROL OUTPUT D e h u m i d i f i c a t i o n SP Setpoint e g 50 rH 100 Proportional Band e g 5 rH SP 0 Humidity rH 0 rH 100 rH LOOP OUTPUT H u m i d i f i c a t i o n 0 instead of 0...

Page 14: ...to open the operating mode does not change until the countdown timer has expired DIGITAL INPUT DELAY setting Note Resistive Inputs as a Digital Input operate with approx ten seconds delay and are not...

Page 15: ...apter 6 PORT REVERSE see 6 PORT VALVE control chapter reverse operation Analogue Output Scaling Output Limitation Each of the analogue outputs Y1 Y2 Y3 can have Output minimum voltage percentage Outpu...

Page 16: ...The SRC 700 controller can be configured to control Belimo 6 Port valve by selecting 6 Port or 6 Port Reverse mode for the analogue output Y1 Y2 Y3 The diagram below illustrates the operation Note Ana...

Page 17: ...ensor 2 Fault The typical alarm reasons are External sensor 1 Res1 fault when activated out of range External sensor 2 Res1 fault when activated out of range Built in sensor fault Digital Input Alarm...

Page 18: ...of the temperature control loop Set to 0 to disable 0 1 200 seconds Default 600s Heating Stages Number of Heating Stages 0 None 1 1 Stage Default 2 2 Stages Heating Stage 1 Dir Heating Stage 1 Directi...

Page 19: ...setting Disabled This is done by entering and exiting the System configuration menu Humidity Display Enable Disable Humidity Display if option fitted 0 Disabled 1 Enabled default Digital Input Mode Di...

Page 20: ...fault Anti JAM Valve Exercise 0 14 Days default 0 disabled PWM Period PWM Period SRC 702 SRC 704H 0 120 Seconds default 30 INPUTS OUTPUTS Parameter Name Description Range FAN BOOST TIMES Parameter Nam...

Page 21: ...ACnet Baud Rate 0 9600 Default 1 19200 2 38400 3 57600 4 76800 Parity Only Modbus BACnet versions Parity 0 None Default 1 Odd 2 Even Stop Bits Only Modbus BACnet versions Stop Bits 0 1 Stop Bit Defaul...

Page 22: ...gister Parameter Description Data Type Raw Data Range FUNCTION CODE 01 READ COILS FUNCTION CODE 05 WRITE SINGLE COIL FUNCTION CODE 15 WRITE MULTIPLE COILS 100 OFF Mode Override 0 1 Off On 101 ECO Mode...

Page 23: ...ge Default 2 2 Stages 111 Heating Stage 1 Direction Unsigned 16 0 1 0 Reverse Default 1 Direct 112 Heating Stage 2 Direction Unsigned 16 0 1 0 Reverse Default 1 Direct 113 Number of Cooling Stages Uns...

Page 24: ...put Y2 Override Value Unsigned 16 0 1000 0 100 0 10 0V Default 0 136 Analogue Output Y3 Override Value Unsigned 16 0 1000 0 100 0 10 0V Default 0 137 Y1 Minimum Output Unsigned 16 0 1000 0 100 0 Defau...

Page 25: ...Unsigned 16 0 4 0 Lock mode disabled default 1 On Off workable only 2 Temp settings only available 3 All buttons disabled 156 Lock Mode Password Unsigned 16 0 9999 0000 9999 157 Boost Time Unsigned 16...

Page 26: ...ride Level 1 100 On Off 50 3 Levels 33 4 Levels 3 Override Level 2 100 3 Levels 66 4 Levels 4 Override Level 3 100 4 Levels 178 Override Blinds Notes After overriding the level the parameter returns t...

Page 27: ...gned 16 0 2400 0 2400 Default 2200 215 Tuesday Switching Time 1 Target Unsigned 16 0 3 0 Comfort Default 1 ECO 2 Off 3 Boost 216 Tuesday Switching Time 2 Target Unsigned 16 0 3 217 Tuesday Switching T...

Page 28: ...0 2400 0 2400 Default 0600 261 Sunday Switching Time 2 Unsigned 16 0 2400 0 2400 Default 1000 262 Sunday Switching Time 3 Unsigned 16 0 2400 0 2400 Default 1300 263 Sunday Switching Time 4 Unsigned 16...

Page 29: ...ue Please note AV1 AV10 are Read Only 31 AV 0 Built In Sensor Read Only2 AV 1 RI_1 RI1 Temperature AI1 R O2 AV 2 RI_2 RI2 Temperature AI2 R O2 AV 3 Target Calculated Setpoint R O2 AV 4 Humidity Read O...

Page 30: ...ry Properties 40106 Setpoint Adjust Minimum REAL 20 0 0 0 C F Default 3 0 40107 Setpoint Adjust Maximum REAL 0 0 20 0 C F Default 3 0 40110 Number of Heating Stages Unsigned 0 None 1 1 Stage Default 2...

Page 31: ...ult Cooling Stage 1 Unsigned 40143 Anti JAM Time out Unsigned 0 14 Days 0 Disabled Default 40144 RI1 Mode Unsigned 0 Disabled default 1 Room NTC10 Control 2 Floor NTC10 High Low Lim 3 Aux Loop 4 Netwo...

Page 32: ...midity Unsigned 0 Disabled 1 Enabled default 40165 Show Swap Temperature Units Icon Unsigned 0 Disabled default 1 Enabled 40166 Zone 1 Room Sensor Text Unsigned 1 Room Default 2 Floor 3 Outside 4 Zone...

Page 33: ...seconds Default 0 0 Infinite Delay 40190 Aux Heating Loop Proportional Band Unsigned 1 0 50 0 C F Default 4 C 40191 Aux Heating Loop Control Integral Action Unsigned 0 1 200 seconds Default 600 40192...

Page 34: ...61 34 34 Online store www syxthsense com Enquiries T 44 0 1392 875 414 E info syxthsense com Dimensions 88mm 3 46 14 5mm 0 56 52mm 2 05 43mm 1 69 112mm 4 41 88mm 3 46 52mm 2 05 112mm 4 41 53mm 2 09 49...

Reviews: