background image

SyxthSense Ltd

Copyright © 2020 SyxthSense Ltd. All rights reserved - 11/2020 

PS 

CT2.161

 - 12/34

Online store: 

www.syxthsense.com

Enquiries: T:

  +44 (0)1392 875 414   

E:

 [email protected]

The Fan Off Delay defines time how long the fan overruns in the deadzone (after no demand). E.g. by 
setting the Fan Off Delay to 30 seconds, the fan switches off after the Htg/Clg Stage 1 demand has 
remained within the deadzone for 30 seconds (example above).

If maximum speed is required to be set for the fan, this is confugured by setting the maximum level in 
the analogue output (Y1, Y2, Y3) scaling. As default fan speed is configured for Y1.

In ECO mode the Fan Speed control follows the same principle as in the COMFORT mode. In OFF 
mode the fan is Off unless frost has been detected in which case the fan output is set to 33%.

Automatic Fan Speed Display

Fan speed can be displayed on the 
screen using coloured bar indicating 
the speed and rotating fan icon. The 
display is enabled through the Fan 
Speed Display parameter. 

Room

20

.1

°C

FAN SPEED INDICATION AND 
CONTROL, AUTO IS DISPLAYED 
WHEN UNDER AUTOMATIC 
CONTROL. WHEN RUNNING 

Target

21

.5

°C

FAN SPEED INDICATION IN 
AUTOMATIC CONTROL

0% to 8%

A

A

A

A

A

A

A

A

8% to 25%

25% to 41%

41% to 58%

58% to 74%

74% to 92%

92% to 100%

Options are:-

NONE; no display (Default)

NO INPUT; no user adjustment 

0-1; Off/On

0-1-2; 2-Speed

0-1-2-3; 3-Speed

0-1-2-3-4-5-6; 6-Speed

When in Automatic control ’A’ is 
displayed above the coloured bar. The 
number of bars displayed depends on 
the fan speed - switching levels described above.

Manual Fan Speed Override

The Fan Speed Display parameter 
is used to configure Manual Fan 
Speed Override options; On/Off, 
2-Speed, 3-Speed or 6-Speed.

ON/OFF MANUAL
FAN OVERRIDE

3-SPEED MANUAL
FAN OVERRIDE

2-SPEED MANUAL
FAN OVERRIDE

M

AFTER FULL SPEED AUTO 
OPTION IS AVAILABLE TO 
RETURN BACK TO AUTO-
MATIC CONTROL

6-SPEED MANUAL FAN 
CONTROL

M

17%

33%

0% 

50%

67%

83%

100%

A

Auto

SPEED SET BY 
CONTROLLER

100%

0% 

50%

100%

0% 

33%

67%

0% 

100%

M

M

M

M

M

M

M

M

M

M

M

M

A

Auto

SPEED SET BY 
CONTROLLER

A

Auto

SPEED SET BY 
CONTROLLER

A

Auto

SPEED SET BY 
CONTROLLER

Once activated the user can 
override the Fan Speed by 
touching the Fan Icon on the 
screen. The desired speed can be 
set by touching multiple times on 
the screen. When Manual override 
is active ’M’ is displayed above the 
coloured speed bar.

In ECO mode Manual Override is 
active. In OFF mode manual 
override is disabled.

NOTE: Manual Fan Override sets 
the Fan Speed to defined values as described above and the Min. Fan Level parameter is 
ignored. 

Auxiliary Heating Control 
Loop 

The SRC-700 series controllers have an auxiliary heating temperature control loop. The auxiliary 
control loop provides additional PI-control function for applications where second control loop is 
required e.g. second zone temperature control for bathrooms. The auxiliary control loop is activated 
by selecting Aux control for RI1 or RI2 input. 

Note: RI2 is not available with SRC-701.

CO2 Sensor Control Loop 
Operation (SRC-70x-CO2 
Models)

The CO2 models can measure and control 
the CO2 level. This can then be used in 
demand based control applications. The 
CO2 control output can then be configured 
to linked to any of the physical control 
outputs Y1, Y2 or Y3, or used in maximum 
demand control (MAX VAV, MAX FAN 
options)

CONTROL 

OUTPUT

CO2 Control

SP= Setpoint e.g. 800ppm
PB = Proportional Band

100%

PB

e.g 400ppm

SP

0%

CO2 Level

-

+

0 ppm

2000 ppm

LOOP OUTPUT 

The CO2 control loop output corresponds 
to the CO2 setpoint and the CO2 
proportional band. If configured as Direct 
Control (typical), then if the CO2 level 
increases above the setpoint the loop output starts to modulate to 100%. When the CO2 level is the 
amount of the Proportional Band above the setpoint, the loop output is 100%. The configuration is 
done via the configuration parameters. The CO2 control loop can also be configured to operate as 

Summary of Contents for SRC-P-700 Series

Page 1: ...ic Summer Winter Time Change Over Product sheet CT2 161 Type SRC P 700 Product Selection Table 1 2 3 4 5 6 1 Device type Touchscreen Room Controller 2RI 1DI 3AO htg clg fan Schedule SRC P 700 Touchscr...

Page 2: ...maximum 63 devices MAC Addressing 0 127 via Touchscreen Device ID Default 651000 MAC Address Adjustable Communication 9k6 19k2 38k4 57k6 76k8 Baud Parity None Even Odd 1 or 2 Stop Bits adjustable thr...

Page 3: ...ommon RI1 Remote NTC10 Temperature Sensor Input 1 0 10V with AI option RI2 Remote NTC10 Temperature Sensor Input 2 0 10V with AI option Din Volt Free Digital Input Contact dry contact 485A Modbus BACn...

Page 4: ...nput 1 0 10V with AI option RI2 Remote NTC10 Temperature Sensor Input 2 0 10V with AI option Din Volt Free Digital Input Contact dry contact 485A Modbus BACnet MS TP RS485 A Connection 485B Modbus BAC...

Page 5: ...n Speed 1 On Off Valve RCOM Relay Common RLY2 230V 7A Relay Fan Speed 2 RLY3 230V 7A Relay Fan Speed 3 TR2 24Vac 1A Triac switched to 0V default Cooling PWM 24V 24Vac dc Supply G0 0V Common TR1 24Vac...

Page 6: ...Ring modulates based on how far from the Effective Heating Cooling Setpoint the temperature is When the difference is 2 C 3 6 F the Energy Ring is at full density calcSP HDz MEASURED TEMPERATURE CDz...

Page 7: ...in the stand by level switches the backlight OFF The screen backlight is automatically activated when it is touched Further Settings and Information The FURTHER SETTINGS screen shows additional user...

Page 8: ...re to fluctuate around the setpoint without heating or cooling valves starting to open The SRC has a built in lock that prevents cooling and heating demands to be on simultaneously The deadzone has an...

Page 9: ...target setpoint on the display is not changed during the limitation The limit icon indicates active limitation To see the effective limited setpoint enter Controller Status and Information display Not...

Page 10: ...C 6 0 0 6 0 1 6 0 2 0 1 0 V d c S R C 6 0 2 P W M Note If the 7 Day Schedule has been activated the device starts to use the operating mode set at the next switching point e g if the next switching p...

Page 11: ...chedule point regardless of the Boost Time or Current Measurement Please note that at the next switching time the target COMFORT ECO OFF BOOST must be different from the target in the current period i...

Page 12: ...O MATIC CONTROL 6 SPEED MANUAL FAN CONTROL M 17 33 0 50 67 83 100 A Auto SPEED SET BY CONTROLLER 100 0 50 100 0 33 67 0 100 M M M M M M M M M M M M A Auto SPEED SET BY CONTROLLER A Auto SPEED SET BY C...

Page 13: ...e actuators 100 CONTROL OUTPUT D e h u m i d i f i c a t i o n SP Setpoint e g 50 rH 100 Proportional Band e g 5 rH SP 0 Humidity rH 0 rH 100 rH LOOP OUTPUT H u m i d i f i c a t i o n 0 instead of 0...

Page 14: ...to open the operating mode does not change until the countdown timer has expired DIGITAL INPUT DELAY setting Note Resistive Inputs as a Digital Input operate with approx ten seconds delay and are not...

Page 15: ...apter 6 PORT REVERSE see 6 PORT VALVE control chapter reverse operation Analogue Output Scaling Output Limitation Each of the analogue outputs Y1 Y2 Y3 can have Output minimum voltage percentage Outpu...

Page 16: ...The SRC 700 controller can be configured to control Belimo 6 Port valve by selecting 6 Port or 6 Port Reverse mode for the analogue output Y1 Y2 Y3 The diagram below illustrates the operation Note Ana...

Page 17: ...ensor 2 Fault The typical alarm reasons are External sensor 1 Res1 fault when activated out of range External sensor 2 Res1 fault when activated out of range Built in sensor fault Digital Input Alarm...

Page 18: ...of the temperature control loop Set to 0 to disable 0 1 200 seconds Default 600s Heating Stages Number of Heating Stages 0 None 1 1 Stage Default 2 2 Stages Heating Stage 1 Dir Heating Stage 1 Directi...

Page 19: ...setting Disabled This is done by entering and exiting the System configuration menu Humidity Display Enable Disable Humidity Display if option fitted 0 Disabled 1 Enabled default Digital Input Mode Di...

Page 20: ...fault Anti JAM Valve Exercise 0 14 Days default 0 disabled PWM Period PWM Period SRC 702 SRC 704H 0 120 Seconds default 30 INPUTS OUTPUTS Parameter Name Description Range FAN BOOST TIMES Parameter Nam...

Page 21: ...ACnet Baud Rate 0 9600 Default 1 19200 2 38400 3 57600 4 76800 Parity Only Modbus BACnet versions Parity 0 None Default 1 Odd 2 Even Stop Bits Only Modbus BACnet versions Stop Bits 0 1 Stop Bit Defaul...

Page 22: ...gister Parameter Description Data Type Raw Data Range FUNCTION CODE 01 READ COILS FUNCTION CODE 05 WRITE SINGLE COIL FUNCTION CODE 15 WRITE MULTIPLE COILS 100 OFF Mode Override 0 1 Off On 101 ECO Mode...

Page 23: ...ge Default 2 2 Stages 111 Heating Stage 1 Direction Unsigned 16 0 1 0 Reverse Default 1 Direct 112 Heating Stage 2 Direction Unsigned 16 0 1 0 Reverse Default 1 Direct 113 Number of Cooling Stages Uns...

Page 24: ...put Y2 Override Value Unsigned 16 0 1000 0 100 0 10 0V Default 0 136 Analogue Output Y3 Override Value Unsigned 16 0 1000 0 100 0 10 0V Default 0 137 Y1 Minimum Output Unsigned 16 0 1000 0 100 0 Defau...

Page 25: ...Unsigned 16 0 4 0 Lock mode disabled default 1 On Off workable only 2 Temp settings only available 3 All buttons disabled 156 Lock Mode Password Unsigned 16 0 9999 0000 9999 157 Boost Time Unsigned 16...

Page 26: ...ride Level 1 100 On Off 50 3 Levels 33 4 Levels 3 Override Level 2 100 3 Levels 66 4 Levels 4 Override Level 3 100 4 Levels 178 Override Blinds Notes After overriding the level the parameter returns t...

Page 27: ...gned 16 0 2400 0 2400 Default 2200 215 Tuesday Switching Time 1 Target Unsigned 16 0 3 0 Comfort Default 1 ECO 2 Off 3 Boost 216 Tuesday Switching Time 2 Target Unsigned 16 0 3 217 Tuesday Switching T...

Page 28: ...0 2400 0 2400 Default 0600 261 Sunday Switching Time 2 Unsigned 16 0 2400 0 2400 Default 1000 262 Sunday Switching Time 3 Unsigned 16 0 2400 0 2400 Default 1300 263 Sunday Switching Time 4 Unsigned 16...

Page 29: ...ue Please note AV1 AV10 are Read Only 31 AV 0 Built In Sensor Read Only2 AV 1 RI_1 RI1 Temperature AI1 R O2 AV 2 RI_2 RI2 Temperature AI2 R O2 AV 3 Target Calculated Setpoint R O2 AV 4 Humidity Read O...

Page 30: ...ry Properties 40106 Setpoint Adjust Minimum REAL 20 0 0 0 C F Default 3 0 40107 Setpoint Adjust Maximum REAL 0 0 20 0 C F Default 3 0 40110 Number of Heating Stages Unsigned 0 None 1 1 Stage Default 2...

Page 31: ...ult Cooling Stage 1 Unsigned 40143 Anti JAM Time out Unsigned 0 14 Days 0 Disabled Default 40144 RI1 Mode Unsigned 0 Disabled default 1 Room NTC10 Control 2 Floor NTC10 High Low Lim 3 Aux Loop 4 Netwo...

Page 32: ...midity Unsigned 0 Disabled 1 Enabled default 40165 Show Swap Temperature Units Icon Unsigned 0 Disabled default 1 Enabled 40166 Zone 1 Room Sensor Text Unsigned 1 Room Default 2 Floor 3 Outside 4 Zone...

Page 33: ...seconds Default 0 0 Infinite Delay 40190 Aux Heating Loop Proportional Band Unsigned 1 0 50 0 C F Default 4 C 40191 Aux Heating Loop Control Integral Action Unsigned 0 1 200 seconds Default 600 40192...

Page 34: ...61 34 34 Online store www syxthsense com Enquiries T 44 0 1392 875 414 E info syxthsense com Dimensions 88mm 3 46 14 5mm 0 56 52mm 2 05 43mm 1 69 112mm 4 41 88mm 3 46 52mm 2 05 112mm 4 41 53mm 2 09 49...

Reviews: