167
Zone 2 Floor Sensor Text
Default: 2 = Floor
Unsigned 16
0..16
0 = Disabled
1 = Room
2 = Floor
3 = Outside
4 = Zone 1
5 = Zone 2
6 = Zone 3
7 = Bathroom
8 = Sauna
9 = Bedroom
10 = Kitchen
11 = Cooler
12 = Flow
13 = Hot Water
14 = Tank
15 = Pool
16 = Cabin
168
Zone 3 Outside Sensor Text
Default: 3 = Outside
Unsigned 16
0..16
169
Alarm 1 Source
Unsigned 16
0..3
0 = CO2
1 = Room (Temperature)
2 = Humidity
3 = None (Default)
170
Alarm 1 Amber Switching Point
Unsigned 16
0..5000
0..5000 (Default 0)
171
Alarm 1 Red Switching Point
Unsigned 16
0..5000
0..5000 (Default 0)
172
Alarm 1 Hysteresis
Unsigned 16
0..5000
0..5000 (Default 0)
173
Alarm 2 Source
Unsigned 16
0..3
0 = CO2
1 = Room (Temperature)
2 = Humidity
3 = None (Default)
174
Alarm 2 Amber Switching Point
Unsigned 16
0..5000
0..5000 (Default 0)
175
Alarm 2 Red Switching Point
Unsigned 16
0..5000
0..5000 (Default 0)
176
Alarm 2 Hysteresis
Unsigned 16
0..5000
0..5000 (Default 0)
177
Override Lights
Notes: After overriding the level the parameter
returns to 0. The lights object takes the last
action (network or user).
Notes: Override Level 1 is the next level after
0% and depends on the configuration. For
On/Off = 100%, for 3-levels = 50%, for 4-levels
= 33%. And so on.
Unsigned 16
0..5
0 = None (default)
1 = Override Level (0%)
2 = Override Level 1
(100%-On/Off, 50%-3 Levels, 33%
- 4 Levels)
3 = Override Level 2
(100%-3-Levels, 66% - 4 Levels)
4 = Override Level 3
(100% - 4 Levels)
178
Override Blinds
Notes: After overriding the level the parameter
returns to 0. The blinds object takes the last
action (network or user).
Notes: Override Level 1 is 100% for On/Off
config, 25% for 4-steps config.
Unsigned 16
0..5
0 = None (default)
1 = Override Level 0 (0%)
2 = Override Level 1 (25/100%)
3 = Override Level 2 (50%)
4 = Override Level 3 (75%)
5 = Override Level 4 (100%)
179
Override Lock Mode
Notes: After overriding the Lock to On/Off the
parameter returns to 0.
Unsigned 16
0..2
0 = None (default)
1 = Override On
2 = Override Off
180
Maintenance Mode Password
Unsigned 16
0..9999
0000...9999 (default 6666)
181
Staff Code
Unsigned 16
0..9999
0000...9999 (default 0000)
182
PWM Cycle (Only SRC-702/604H)
Unsigned 16
0..120
0..120 None (default 30, 0=on/off)
183
Digital Output 1 Network Override (Overrides
DO1 directly, local, only SRC-702)
Unsigned 16
0..2
0 = No Override (Default)
1 = Override Output On
2 = Override Output Off
184
Digital Output 2 Network Override (Overrides
DO2 directly, local, only SRC-702)
Unsigned 16
0..2
0 = No Override (Default)
1 = Override Output On
2 = Override Output Off
185
Heating/Cooling Changeover Min Temperature
Unsigned 16
0...950
0.0...95.0°C/°F (Default 20°C)
186
Heating/Cooling Changeover Max Temperature
Unsigned 16
0...950
0.0...95.0°C/°F (Default 25°C)
187
Fan Speed Override
Unsigned 16
0..7
0 = Auto
1 = Manual Off
2 = Manual Level 1
3 = Manual Level 2
4 = Manual Level 3
5 = Manual Level 4
6 = Manual Level 5
7 = Manual Level 6
Register
Parameter Description
Data Type
Raw Data
Range