Note1: Objects are used to change the mode ON or OFF. The mode takes the last action e.g. after
overriding the ECO mode on via BO(1), the user can cancel the ECO mode from the screen. The
present value field indicates the current state.
Note2: RO = "Read Only". Not possible to write to the object.
Note3: It is possible to override the output level without changing the Y1/Y2/Y3 mode to network. The
object returns to use the internal logic value once the priority inputs have been set to ’null’.
App_Config Objects
NOTE: Application Configuration Objects expose the configuration parameters over the
BACnet. However please check if your BACnet client can support Proprietary Object types to
be able to access these parameters. Alternatively set the configuration parameters through the
SRC touchscreen.
Property Name /ID
Attributes
Range
Default
Required
Object
Properties
Object Identifier
R
proprietary-128
Object Name
R/W
"Config1"
Object Type
R
proprietary-128
Optional
Properties
None
Property ID
Description
BACnet Data Type
Range
Proprietary
Properties
40106
Setpoint Adjust Minimum
REAL
-20.0..0.0 °C/°F (Default -3.0)
40107
Setpoint Adjust Maximum
REAL
0.0..20.0 °C/°F (Default 3.0)
40110
Number of Heating Stages
Unsigned
0 = None
1 = 1-Stage (Default)
2 = 2-Stages
40111
Heating Stage 1 Direction
Unsigned
0 = Reverse (Default), 1 = Direct
40112
Heating Stage 2 Direction
Unsigned
0 = Reverse (Default), 1 = Direct
40113
Number of Cooling Stages
Unsigned
0 = None
1 = 1-Stage (Default)
2 = 2-Stages
40114
Cooling Stage 1 Direction
Unsigned
0 = Reverse, 1 = Direct (Default)
40115
Cooling Stage 2 Direction
Unsigned
0 = Reverse, 1 = Direct (Default)
40116
High Limit Setpoint
REAL
0..95°C/°F (Default 35.0°C)
40117
Low Limit Setpoint
REAL
0..95°C/°F (Default 16.0°C)
40118
Limit Ratio
REAL
0.0..5.0 (0.0=Disabled, Default)
40120
CO2 Proportional Band
Unsigned
10..5000 ppm (Default = 300 ppm)
40121
CO2 Control Integral Action
Unsigned
0..10,000 seconds (Default 0)
40122
CO2 Output Direction
Unsigned
0 = Reverse Acting
1 = Direct Acting (Default)
40124
Humidity Proportional Band
REAL
1.0...100.0 %rH (Default 20.0%)
40125
Humidity Control Integral Action
Unsigned
0..10,000 seconds (Default 0)
40126
Humidification Output Direction
Unsigned
0 = Reverse Acting
1 = Direct Acting (Default)
40127
De-Humidification Output Direction
Unsigned
0 = Reverse Acting
1 = Direct Acting (Default)
40128
Fan Speed Display
Unsigned
0 = No Display (Default)
1 = Display Only (no user adj.)
2 = 0 - 1 (0%, 100%)
3 = 0 - 1 - 2 (0%, 50%, 100%)
4 = 0 - 1 - 2 - 3 (0%, 33%, 66%,100%)
5 = 0 - 1 - 2 - 3 - 4 - 5 - 6